Plan Review Notes For Permit 21051284
Permit Number 21051284
Review Stop B
Sequence Number 2
Notes
Date Text
2021-07-16 14:59:08WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21051284
 ADD: 400 N. FLAGLER DR. # 504
 CONT: SERVICE RESOURCE CBC1263808
 TEL: 561-389-0065
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: JULY 16TH /2021
 ACTION: DENIED
  
 ***********4X FEE / NOTICE!!!!! FLORIDA STATUTE
 553.80(2)(B)*************
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1) 2ND REQUEST. THE FLOOR PLAN DOES NOT INDICATE WHO
 THE AUTHOR OF THE PLAN IS. CERTIFICATION BY CONTRACTOR.
 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT CREATED /
 DREW THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES
 AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME,
 SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE
 LICENSED IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 2) 2ND REQUEST. THE PERMIT APPLICATION INDICATES NEW
 FLOORING, WHERE AND WHAT TYPE. FLOOR INSULATION/
 UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE, MARBLE,
 VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6INCH CONCRETE SLAB / NO DROPPED
 CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 2A) 2ND REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 2B) 2ND REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) 2ND REQUEST. FLAME SPREAD- FBC-B 2020 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B.
  
 3) 2ND REQUEST. PLEASE PROVIDE A NARRATIVE TO IF WHAT
 IS HAPPENING IN THE BATHROOMS, IT APPEARS THERE MAYBE
 RELOCATION OF EITHER TUBS AND OR SHOWERS?
  
 3A) 2ND REQUEST.POST TENSION SLAB/ NEW HOLES. THE PLAN
 IS SILENT AS IF THE LOCATION OF THE EXISTING TUB DRAIN
 IS GOING TO BE REUSED IN THE SAME LOCATION. IF NOT,
 THEN THE FLOOR SLAB WILL NEED TO BE X-RAYED TO FIND THE
 POST TENSION CHORD LOCATIONS. 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3B) 2ND REQUEST. THROUGH-PENETRATIONS FIRESTOP SYSTEMS
 (HORIZONTAL ASSEMBLIES). IF A NEW FLOOR PENETRATION IS
 MADE FOR THE FUTURE SHOWER DRAIN, THEN YOU NEED TO SHOW
 COMPLIANCE WITH THE 2020 FBC-B SECTION 714.5.1.2.
 THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES). THROUGH PENETRATIONS SHALL BE PROTECTED BY
 A THROUGH PENETRATION FIRESTOP SYSTEM INSTALLED IN
 ACCORDANCE WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL
 HAVE AN F RATING / T RATING OF NOT LESS THAN 1 HOUR BUT
 NOT LESS THAN THE REQUIRED RATING OF THE FLOOR
 PENETRATED.
  
 3C) 2ND REQUEST. 2020 FBC-B 2509.2 BASE FOR TILE.
 MATERIALS USED AS A BASE FOR WALL TILE IN TUB AND
 SHOWER AREAS AND WALLS AND CEILING PANELS IN SHOWER
 AREAS SHALL BE OF MATERIALS LISTED IN TABLE 2509.2 AND
 INSTALLED IN ACCORDANCE WITH MANUFACTURER?S
 RECOMMENDATIONS. WATER RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C840 AND THE MANUFACTURE?S
 RECOMMENDATIONS.
  
 3D) 2ND REQUEST. 2020 FBC-B SHOWERS & TUBS 1210.3.
 SHOWER COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER
 HEADS SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO
 A HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  