Plan Review Notes
Plan Review Notes For Permit 21051284
Permit Number 21051284
Review Stop B
Sequence Number 1
Notes
Date Text
2021-06-29 09:36:42WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21051284
 ADD: 400 N. FLAGLER DR. # 504
 CONT: SERVICE RESOURCE CBC1263808
 TEL: 561-389-0065
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JUNE 29TH /2021
 ACTION: DENIED
 1) THE FLOOR PLAN DOES NOT INDICATE WHO THE AUTHOR OF
 THE PLAN IS. CERTIFICATION BY CONTRACTOR. 107.3.4.3.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
 2) THE PERMIT APPLICATION INDICATES NEW FLOORING, WHERE
 AND WHAT TYPE. FLOOR INSULATION/ UNDERLAYMENT (FBC-B
 2020) FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING
 ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED
 FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET
 THE QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS
 FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED
 CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 2B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 2C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B.
  
 3) PLEASE PROVIDE A NARRATIVE TO IF WHAT IS HAPPENING
 IN THE BATHROOMS, IT APPEARS THERE MAYBE RELOCATION OF
 EITHER TUBS AND OR SHOWERS?
  
 3A) POST TENSION SLAB/ NEW HOLES. THE PLAN IS SILENT AS
 IF THE LOCATION OF THE EXISTING TUB DRAIN IS GOING TO
 BE REUSED IN THE SAME LOCATION. IF NOT, THEN THE FLOOR
 SLAB WILL NEED TO BE X-RAYED TO FIND THE POST TENSION
 CHORD LOCATIONS. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 3B) THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES). IF A NEW FLOOR PENETRATION IS MADE FOR THE
 FUTURE SHOWER DRAIN, THEN YOU NEED TO SHOW COMPLIANCE
 WITH THE 2020 FBC-B SECTION 714.5.1.2.
 THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES). THROUGH PENETRATIONS SHALL BE PROTECTED BY
 A THROUGH PENETRATION FIRESTOP SYSTEM INSTALLED IN
 ACCORDANCE WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL
 HAVE AN F RATING / T RATING OF NOT LESS THAN 1 HOUR BUT
 NOT LESS THAN THE REQUIRED RATING OF THE FLOOR
 PENETRATED.
  
 3C) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS
 A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURE?S RECOMMENDATIONS.
  
 3D) 2020 FBC-B SHOWERS & TUBS 1210.3. SHOWER
 COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS
 SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A
 HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  