Plan Review Notes
Plan Review Notes For Permit 21051280
Permit Number 21051280
Review Stop R
Sequence Number 1
Notes
Date Text
2021-07-06 09:47:19PLAN REVIEW ROOFING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
 PERMITS - 105.1 REQUIRED.
  
 2. PROVIDE PRODUCT APPROVALS
 R905.1.1.1UNDERLAYMENT FOR ASPHALT, METAL, MINERAL
 SURFACED, SLATE AND SLATE-TYPE ROOF COVERINGS.
 UNDERLAYMENT FOR ASPHALT SHINGLES, METAL ROOF SHINGLES,
 MINERAL SURFACED ROLL ROOFING, SLATE AND SLATE-TYPE
 SHINGLES, AND METAL ROOF PANELS SHALL COMPLY WITH ONE
 OF THE FOLLOWING METHODS:
 1.THE ENTIRE ROOF DECK SHALL BE COVERED WITH AN
 APPROVED SELF-ADHERING POLYMER-MODIFIED BITUMEN
 UNDERLAYMENT COMPLYING WITH ASTM D1970
 2.A MINIMUM 4-INCH-WIDE (102 MM) STRIP OF SELF-ADHERING
 POLYMER-MODIFIED BITUMEN MEMBRANE COMPLYING WITH ASTM
 D1970
 3.A MINIMUM 33/4-INCH WIDE (96 MM) STRIP OF
 SELF-ADHERING FLEXIBLE FLASHING TAPE COMPLYING WITH
 AAMA 711, LEVEL 3
 4.TWO LAYERS OF ASTM D226 TYPE II OR ASTM D4869 TYPE
 III OR TYPE IV UNDERLAYMENT SHALL BE INSTALLED AS
 FOLLOW
 5.TWO LAYERS OF A REINFORCED SYNTHETIC UNDERLAYMENT
 THAT HAS A PRODUCT APPROVAL AS AN ALTERNATIVE TO
 UNDERLAYMENT COMPLYING WITH ASTM D22
  
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  
  