| Date |
Text |
| 2021-07-06 10:10:27 | PLAN REVIEW BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2017 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | |
| | 1. PROVIDE A SITE PLAN/DRAINAGE PLAN/BOUNDRY LINE |
| | SURVEY |
| | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED |
| | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY |
| | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF |
| | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, |
| | DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES |
| | AND THE PROPOSED FINISHED GRADES, DEPICTING THE |
| | PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD |
| | AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT |
| | SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| | INCLUDED BOUNDARY LINE SURVEY. |
| | |
| | FBC R401.3 SITE DRAINAGE |
| | PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH |
| | FBC R401.3 DRAINAGE. |
| | |
| | 2. PROVIDE AN ENERGY SUBMITTAL. (NOT CORRECTED. PROVIDE |
| | R VALUE FOR CLOSED ROOF) |
| | DESIGNER SHALL INDICTATE THE R VALUE OF CEILING AND |
| | WALL INSULATION ON THE PLANS. |
| | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| | COMPLIANCE BY SECTION 405. |
| | |
| | 3. PROVIDE COVER SHEET AND INSTALLATION INSTRUCTIONS |
| | FOR EXTERIOR DOORS. CORRECTED |
| | THE COVER SHEET PROVIDES THE APPROVAL NUMBER, CODE |
| | VERSION, AND STATUS, FBC R 301. |
| | (COVER SHEETS ARE NOT REQUIRED FOR MIAMI DADE NOAS.) |
| | |
| | 4. THE PLANS CALL FOR IMPACT RATED WINDOWS. NOA |
| | 20-0402.01 IS FOR NON-IMPACT RATED WINDOWS. |
| | EITHER PROVIDE AN NOA FOR IMPACT RATED WINDOWS OR A |
| | SCHEDULE FOR OPENING NPROTECTIVE DEVICES OR ASSEMBLIES |
| | WITH CURRENT PRODUCT APPROVALS OF DEVICES. |
| | |
| | 5. PROVIDE PRODUCT APPROVALS FOR WINDOW MULLIONS. (NOT |
| | CORRECTED) |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |