| Plan Review Notes For Permit 21051240 |
| Permit Number |
21051240 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-05-27 13:12:48 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE PLAN SHEET INDICATES CPVC 2 1/2" FOR THE | | | UNDERGROUND. | | | | | | PER NFPA 24, THAT DOES NOT MEET THE STANDARD PER TABLE | | | 10.1.1 | | | | | | 10.1* PIPING MATERIALS. | | | 10.1.1* LISTING. PIPING SHALL BE LISTED FOR FIRE | | | PROTECTION SERVICE | | | OR SHALL COMPLY WITH THE STANDARDS IN TABLE 10.1.1. | | | | | | PLASTIC | | | POLYVINYL CHLORIDE (PVC) PRESSURE PIPE, 4 IN. | | | THROUGH 12 IN., FOR WATER DISTRIBUTION - AWWA C900 | | | | | | POLYVINYL CHLORIDE (PVC) PRESSURE PIPE, 14 IN. | | | THROUGH 48 IN., FOR WATER DISTRIBUTION - AWWA C905 | | | | | | THERE WERE NO MANUFACTURES SPECIFICATION SHEETS PROVIED | | | SHOWING COMPLIANCE | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | |
|