| 2021-09-15 13:00:54 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21051228 |
| | 9/15//2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN |
| | CAPS FOR FURTHER CLARIFICATION. |
| | |
| | 3) FAILED. A5.01- DETAIL 2/A5.01: THE DOOR SHALL NOT |
| | SWING INTO THE CLEAR FLOOR SPACE OF THE LAVATORY- |
| | SECTION 603.2.3 FBC ACC. DETAIL HAS BEEN CORRECTED |
| | HOWEVER DETAIL 4 WAS OVERLOOKED. PLEASE SEE THE |
| | EXCEPTION UNDER SECTION 603.2.3. |
| | |
| | 10) FAILED. P1.0U1: SHOW THE BRANCH DRAIN LINE FOR THE |
| | JANITOR'S SINK- SECTION 107.2.1 WPB. SECTION 1003.3.1 |
| | REQUIRES THAT THE MOP SINK DRAIN INTO THE GREASE WASTE |
| | INTERCEPTOR, HOWEVER THE GREASE WASTE INTERCEPTOR AND |
| | WASTE LINE HAVE BEEN REMOVED FROM THE PLAN AND |
| | DESIGNATED AS ?FUTURE?. |
| | |
| | 18) FAILED. P1.01: PROVIDE A WATER HEATER INSTALLATION |
| | DETAIL SHOWING HOT, COLD, AND RETURN PIPING |
| | CONNECTIONS, RECIRCULATION PUMP, EXPANSION TANK, SHUT |
| | OFF VALVES, CHECK VALVES, RELIEF VALVE AND DISCHARGE |
| | PIPE, DRAIN PAN AND DRAIN PAN LINE INCLUDING |
| | TERMINATION LOCATION- SEE CHAPTER 5 FBC P. DRAIN PAN, |
| | DRAIN PAN LINE RUN AND TERMINATION LOCATION NOT |
| | PROVIDED. |
| | |
| | 19) FAILED. P0.00: PROVIDE PLUMBING PIPING |
| | SPECIFICATIONS, AND THE TYPE AND THICKNESS OF HOT WATER |
| | PIPE INSULATION- TABLE C403.2.10 FBC EC. THE TABLE |
| | PASTED ON THE SHEET IS INCORRECT. TABLE C403.2.10 FBC |
| | EC REQUIRES MINIMUM 1.5 INCHES THICK INSULATION FOR THE |
| | 2-INCH HW PIPING. |
| | |
| | 20) FAILED. A1.01: PROVIDE FINISHED WALL DETAILS FOR |
| | THE MOP SINK SURROUND- SECTION 1210.2.2 FBC B. PLEASE |
| | PROVIDE A SUBMITTAL FOR THE WALL SURROUND PANEL THAT |
| | INDICATES THE MATERIAL HAS A SMOOTH, HARD, NONABSORBENT |
| | SURFACE AS REQUIRED BY SECTION 1210.2.2 FBX B. |
| | |
| | 22) FAILED. A1-R) & P1.R0: PLEASE SHOW THE SCUPPER AND |
| | OVERFLOW LOCATIONS ON P1.RO AND PROVIDE SIZING |
| | CALCULATIONS AND INSTALLATION DETAILS- SECTION 1108.3 |
| | FBC P. PLEASE INCLUDE ELEVATION VIEWS SHOWING THE TYPE |
| | AND SIZE OF DOWNSPOUTS, DOWNSPOUT SCUPPER CONNECTION |
| | DETAIL, AND DISCHARGE LOCATIONS OF THE DOWNSPOUTS. A) |
| | THE DOWNSPOUTS AND DISCHARGE LOCATIONS ARE NOT SHOWN ON |
| | THE ELEVATION DRAWING A3.02. B) PLEASE PROVIDE SIZING |
| | CALCULATIONS FOR THE SYSTEM IN ACCORDANCE WITH SECTIONS |
| | 1106.1 & 1108.3 FBC P. PLEASE INCLUDE THE RAINFALL RATE |
| | THAT THE CALCULATIONS ARE BASED ON. C) SHEET P1.0U1 |
| | SHOWS A TRENCH DRAIN THAT IS CONVEYING STORM DRAINAGE- |
| | PLEASE SHOW THE PIPING INLET AND OUTLET LOCATIONS AND |
| | CONNECTIONS TO THE SYSTEM ON THE ISOMETRIC DRAWING- |
| | P0.04. |
| | |
| | 23) FAILED. P1.01 & P1.R0: SHOW HOW THE RAIN WATER FROM |
| | THE ROOF WILL BE DRAINED AWAY FROM THE BUILDING TO AN |
| | APPROVED PLACE OF DISPOSAL- SECTION 1101.1 FBC B. THE |
| | PRIMARY SYSTEM DISCHARGE LOCATIONS HAVE NOT BEEN |
| | PROVIDED ON P1.01, P1.R0, OR P0.04. THERE ARE NO |
| | CHANGES TO THE CIVIL PLANS TO SHOW POINTS OF CONNECTION |
| | TO THE STORM DRAIN SYSTEM. |
| | |
| | PLEASE NOTE REVIEW OF CORRECTED PLANS MAY RESULT IN |
| | ADDITIONAL COMMENTS. WHEN RESUBMITTING, IT IS HELPFUL |
| | TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG |
| | WITH THE CITY RE-SUBMITTAL FORM. |
| | |