| Plan Review Notes For Permit 21051228 |
| Permit Number |
21051228 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-06-22 15:54:07 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21051228 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE SHOW THE ROOF ACCESS ON SHEET M1.02 | | | | | | 2) PLEASE PROVIDE THE COMPLETE COMCHECK REPORT FOR THE | | | MECHANICAL EQUIPMENT IN THE SUPPORTING DOCUMENTS FILES. | | | FBC EC C403.2.1 | | | | | | 3) PLEASE LABEL THE UNIT THAT IS CONDITIONING THE BACK | | | OF HOUSE. | | | | | | 4) PROVIDE THE MECHANICAL EQUIPMENT SIZING AND THE | | | COMPLETE MECHANICAL DESIGN FOR THE COMMON AREAS | | | INCLUDING THE OUTDOOR AIR CALCULATIONS. FBC 107.2.1 | | | | | | 5) PLEASE IDENTIFY THE RTU THAT IS CONDITIONING THE | | | FOOD PLAZA AREA. FBC 107.2.1 | | | | | | 6) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THE | | | FOOD PLAZA BASED ON FBC M 403.3.1.1 AND TABLE 403.3.1.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|