| Plan Review Notes For Permit 21051188 |
| Permit Number |
21051188 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-11-01 11:39:14 | 3RD REVIEW FBC-2020 PLUMBING | | | PERMIIT- 21051188 | | | 11/1/21 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS A4.03 & A4.04: PLEASE CORRECT THE HEIGHTS OF | | | THE MIRRORS TO INDICATE 40-INCHES FROM THE FINISHED | | | FLOORS TO THE BOTTOM EDGES OF THE REFLECTIVE SURFACES- | | | SECTION 603.3 FBC ACC. | | | | | | 2) P2.3: PLEASE SHOW THE CONDENSATE PIPING RUNS TO THE | | | ROOF DRAINS AND PROVIDE SUPPORT DETAILS- SECTION | | | 314.2.1 & TABLE 308.5 FBC P. | | | | | | 3) P2.1 & P5.1: PLEASE CORRECT THE ISOMETRIC DRAWINGS | | | SHOWING THE 3-INCH DRAIN PIPE FROM THE FLOOR SINK AT | | | THE COFFEE STATION CONNECTING TO THE SANITARY SYSTEM- | | | SECTION 1003.3.1 FBC P. | | | | | | 4) 2ND REQUEST FOR A LIST OF SEPARATE PERMITS AND | | | DEFERRED SUBMITTALS TO BE PLACED ON THE PLANS- SECTION | | | 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|