| 2021-09-14 10:24:51 | 2ND REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21051188 |
| | 9/14/2021 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) FAILED SHEET P6.1 GAS RISER- FBC FG: THE TOTAL BTU |
| | LOAD IN THE COMPLETE SYSTEM TABLE OF 1,179,000 BTU DOES |
| | NOT MATCH THE ISOMETRIC WHICH SHOWS A TOTAL OF 980,000 |
| | BTU. IT APPEARS THAT THE BRANCH LINE TO THE GWH, AND |
| | THE GWH BTU LOAD IS NOT INCLUDED IN THE ISOMETRIC |
| | DRAWING. A) THE ?-INCH PIPE STUB-OUTS ARE UNDERSIZED |
| | USING TABLE 402.4(2) FOR A SYSTEM AT A TDL OF 44 FT. |
| | |
| | E) FAILED. SHOW THE LOCATIONS OF PIPE UNIONS AT MP |
| | REGULATORS- SECTION 410.2 (7). CORRECT THE NOTE TO |
| | INDICATE UNIONS INSTALLED WITHIN 1 FT. OF EITHER SIDE |
| | OF THE REGULATOR, |
| | |
| | F) FAILED. PROVIDE REGULATOR INDEPENDENT VENTING |
| | DETAILS INCLUDING TYPES AND SIZES OF VENT PIPING, |
| | PIPING RUNS AND TERMINATION LOCATIONS- SECTIONS 410.3 & |
| | 410.3.1. VENT PIPING DETAILS FOR THE PRIMARY REGULATOR |
| | NOT PROVIDED, AND NO INFORMATION PROVIDED FOR THE |
| | COOKING LINE REGULATORS- VENTED OR VENTLESS? |
| | H) FAILED. PROVIDE THE PIPE SIZING TABLES USED TO |
| | DESIGN THE SYSTEM- SECTION 402.4. 2-PSI TABLE NOT |
| | PROVIDED. |
| | |
| | 2) FAILED. SHEET P3.1: PROTECTION FROM VEHICLE DAMAGE |
| | IS REQUIRED FOR THE METER, WATER HEATER AND GAS PIPING- |
| | SECTION 303.4 FBC FG. NO INFORMATION PROVIDED ON P3.1. |
| | REVISED SHEET A1.01 INDICATES PROTECTION FOR THE METER |
| | ONLY. |
| | |
| | 6) FAILED. P3.1 & P6.1: PROVIDE COMBUSTION AIR |
| | CALCULATIONS FOR THE GAS-FIRED APPLIANCES AND INDICATE |
| | HOW THE AIR WILL BE SUPPLIED- SECTION 304.1 FBC P. THE |
| | SUBMITTED CALCS ARE USING THE EQUATION FOUND IN SECTION |
| | 304.5.2 WHICH CAN ONLY BE USED WHEN THERE IS A KNOWN |
| | AIR INFILTRATION RATE LESS THAN .40 AIR CHANGES PER |
| | HOUR (ACH). THE CALCULATIONS PROVIDED ARE USING AN ACH |
| | OF 5.6. THE CALCULATION IS ALSO USING 1835 CFMS OF O/A |
| | AS THE BASIS OF THE ACH, HOWEVER THE AIR IS BEING |
| | SUPPLIED MECHANICALLY AS OPPOSED TO INFILTRATION. IF |
| | USING MECHANICAL AIR PLEASE REFER TO SECTION 304.9 AND |
| | PROVIDE THE CALCULATION. IF USING INDOOR AIR THEN THE |
| | REQUIRED VOLUME IS BASED ON 50 CU.FT. PER 1000 BTU OR |
| | IN THIS CASE- 49,000 CU. FT. PLEASE REVIEW SECTION |
| | 304.5.1 BELOW: |
| | THE REQUIRED VOLUME OF INDOOR AIR SHALL BE DETERMINED |
| | IN ACCORDANCE WITH SECTION 304.5.1 OR 304.5.2, EXCEPT |
| | THAT WHERE THE AIR INFILTRATION RATE IS KNOWN TO BE |
| | LESS THAN 0.40 AIR CHANGES PER HOUR (ACH), SECTION |
| | 304.5.2 SHALL BE USED. THE TOTAL REQUIRED VOLUME SHALL |
| | BE THE SUM OF THE REQUIRED VOLUME CALCULATED FOR ALL |
| | APPLIANCES LOCATED WITHIN THE SPACE. ROOMS |
| | COMMUNICATING DIRECTLY WITH THE SPACE IN WHICH THE |
| | APPLIANCES ARE INSTALLED THROUGH OPENINGS NOT FURNISHED |
| | WITH DOORS, AND THROUGH COMBUSTION AIR OPENINGS SIZED |
| | AND LOCATED IN ACCORDANCE WITH SECTION 304.5.3, ARE |
| | CONSIDERED TO BE PART OF THE REQUIRED VOLUME. |
| | |
| | 7) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | GAS-FIRED APPLIANCES- SECTIONS 301.3 & 623.1 FBC FG. |
| | DEFERRED SUBMITTAL REQUEST IS ACCEPTED HOWEVER PLEASE |
| | PROVIDE A LIST ON THE PLANS- SECTION 107.4.3.1 WPB. |
| | |
| | 9) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | REGULATORS AND REGULATOR VENT SYSTEMS- SECTIONS 410.1, |
| | 410.2, & 410.3 FBC FG. DEFERRED SUBMITTAL REQUEST IS |
| | ACCEPTED HOWEVER PLEASE PROVIDE A LIST ON THE PLANS- |
| | SECTION 107.4.3.1 WPB. |
| | |
| | 10) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| | THE TANKLESS WATER HEATER AND INDICATE THE MANUFACTURER |
| | OF THE APPLIANCE IN THE EQUIPMENT SCHEDULE- SECTION |
| | 624.1 FBC FG. IF THE APPLIANCE PRODUCES CONDENSATION |
| | PLEASE SHOW HOW THE DRAINAGE WILL BE CONVEYED AWAY FROM |
| | THE BUILDING TO AN APPROVED PLACE OF DISPOSAL OTHER |
| | THEN ONTO THE SURFACE OF THE SIDEWALK- SECTIONS 307.2 & |
| | 307.3 FBC FG. CONDENSATE DISPOSAL PLAN NOT PROVIDED. |
| | DEFERRED SUBMITTAL REQUEST IS ACCEPTED HOWEVER PLEASE |
| | PROVIDE A LIST ON THE PLANS- SECTION 107.4.3.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |