| 2021-06-23 14:17:52 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21051188 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A0.03 INDICATES A 1-HOUR RATED WALL |
| | SURROUNDING THE COMMUNITY/ BOARD ROOM. PLEASE SHOW THE |
| | REQUIRED PROTECTION IN THESE WALLS AT ALL DUCT |
| | PENETRATIONS ON SHEET M2.2. FBC M607 |
| | |
| | 2) PLEASE ATTACH A NOTE ON THE DRAWING INDICATING THAT |
| | THE KITCHEN HOODS WILL REQUIRE SEPARATE SUBMITTAL FOR |
| | PERMITS AND REVIEWS AND WILL NOT BE REVIEWED ON THIS |
| | PERMIT. |
| | |
| | 3) PLEASE ATTACH A NOTE ON THE DRAWING INDICATING THAT |
| | THE REFRIGERATION EQUIPMENT WILL REQUIRE SEPARATE |
| | SUBMITTAL FOR PERMITS AND REVIEWS AND WILL NOT BE |
| | REVIEWED ON THIS PERMIT. |
| | |
| | 4) PLEASE INCLUDE THE KITCHEN WITH THE OUTDOOR AIR |
| | CALCULATIONS. THE 2020 FBC M NOW IS REQUIRING OUTDOOR |
| | AIR FOR THE COOKING KITCHEN ALONG WITH THE EXHAUST AIR. |
| | FBC M TABLE 403.3.1.1 |
| | |
| | 5) SHEET M2-1: PLEASE SHOW THE RTU FOR THE 2 12X12 |
| | DUCTS SUPPLYING AIR TO THE OFFICE AND CAF? JOSHUA, IT |
| | APPEARS TO BE A BIG HORSESHOE AND DOESN?T SHOW THE RTU. |
| | FBC 107.2.1 |
| | |
| | 6) PLEASE IDENTIFY THE BATHROOM EXHAUST FANS ON THE |
| | DRAWINGS. FBC 107.2.1 |
| | |
| | 7) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE |
| | OF SPACE IN THIS 2 STORY BUILDING INCLUDING STORAGE AND |
| | CORRIDORS, SMALL CAF? ON SECOND FLOOR. FBC M 403.3.1.1 |
| | |
| | 8) PLEASE PROVIDE THE CORRECT OCCUPANCY FROM TABLE |
| | 403.3.1.1 FOR THE AREA LABELED EDUCATION/FLEX ON SHEET |
| | M2.2 FBC M TABLE 403.3.1.1. |
| | |
| | 9) PLEASE SHOW HOW THE KITCHEN RETURN AIR MEETS THE |
| | REQUIREMENTS OF SECTION 601.5 (7) FOR RETURN AIR |
| | OPENINGS. |
| | |
| | 10) SHEET M6.1: PLEASE INCLUDE AIR BALANCE REPORT THAT |
| | INCLUDES ALL BATH EXHAUST AND MEETS THE REQUIREMENTS OF |
| | FBC M 508.1.2 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |