| 2021-07-15 12:18:57 | NEW 2 STORY OFFICE/ CAFE BUILDING |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) OCCUPANCY CLASSIFICATION SHOULD BE SHOWN AS MIXED |
| | B/A2 FBC CHAPTER 3 |
| | 2) PLEASE SHOW THE ACCESSIBLE PATH AND SEATING IN THE |
| | CAFE AND EXTERIOR GARDEN AREA TO COMPLY WITH FBC |
| | A206.2.2 AND 226.1 |
| | 3) PLEASE PROVIDE COMPLETE COPIES OF THE PRODUCT |
| | APPROVALS FOR THE EXTERIOR WINDOWS, DOORS, ROOFING |
| | SYSTEMS, ETC. - ALL PRODUCT APPROVALS NEED TO BE |
| | REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER |
| | OF RECORD OR BE LISTED ON THE DRAWINGS BY THE PRODUCT |
| | APPROVAL NUMBER. FBC WPB 107.2.1 |
| | 4) PLEASE SHOW THE RESTROOM WALL FINISH TO COMPLY WITH |
| | FBC 1210.2.2 (DRYWALL IS NOT CONSIDERED A HARD |
| | SURFACE). |
| | 5) DRAWING A4.04 RESTROOM SHOWS A PARTITION IN FRONT OF |
| | THE TOILET ROOM AND NO DOOR - PLEASE SHOW DOOR |
| | LOCATION. |
| | 6) DRAWING A4.11 - LEVEL 1 ENLARGED PLAN @ WEST STAIR - |
| | NEEDS TO SHOW HAND RAILS ON BOTH SIDES OF THE STAIRS - |
| | FBC 1011.11 |
| | 7) DRAWING A1.01 - SITE DATA - SHOULD SAY 4 ACCESSIBLE |
| | PARKING SPACES. FBC ACCESSIBILITY TABLE 208.2 |
| | 8) DRAWING A5.02 - METAL PAN STAIR- SHOULD SHOW THE |
| | BOTTOM SLOPING HAND RAIL TO CONTINUE 11" PER FBC 1014.6 |
| | 9) THE LIFE SAFETY PLANS SHOW FIRE WALLS AT STAIRWAYS/ |
| | ELEVATOR AND "COMMUNITY BOARD RM" THE WALL DESIGNATIONS |
| | ON THE CONSTRUCTION PLANS DOES NOT SHOW FIRE RATED |
| | WALLS - PLEASE CLARIFY. |
| | 10) DRAWING S-0.00 SHOWS WIND DATA - EXPOSURE "C" USED |
| | - BEING NEAR THE LAKE MANGONIA IT APPEARS THAT EXPOSURE |
| | "D" SHOULD BE USED PER FBC 1609.4.3 |
| | 11) PLEASE SHOW THAT TERMITE PROTECTION IS REQUIRED PER |
| | FBC 1816 |
| | 12) PLEASE PROVIDE DETAILS FOR THE ROOF TOP CANOPY, |
| | ALUMINUM CANOPY, GUARD RAILS, TILT WALL PANELS FAUX |
| | WOOD ROOF DECK. |
| | 13) SEPARATE PERMIT WILL BE REQUIRED FOR PARKING LOT, |
| | DUMPSTER ENCLOSURE, SIGNS, GENERATOR, FENCE. |
| | 14) 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING |
| | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE |
| | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. |
| | THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED |
| | UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| | APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | |