| Plan Review Notes For Permit 21051117 |
| Permit Number |
21051117 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-06-02 09:12:18 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21051117 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PRIVATE PROVIDER MUST SUBMIT REQUIRED DOCUMENTS FOR | | | THIS PROJECT. | | | | | | 2) THE WALK-IN COOLER REFRIGERATION AND THE WALK-IN | | | COOLER SPEC SHEETS DO NOT HAVE THE JOB INFORMATION | | | FILLED IN, PLEASE COMPLETE THIS AS WE MUST HAVE THE JOB | | | INFORMATION TO SEE IT IS SITE SPECIFIC. FBC 107.2.1 | | | | | | 3) THE PRIVATE PROVIDER DID NOT STAMP THE DRAWING. | | | PRIVATE PROVIDER MUST REVIEW AND APPROVE THIS PROJECT | | | BEFORE THE PROJECT IS SUBMITTED TO THE CITY OF WEST | | | PALM BEACH. | | | | | | 4) THERE IS NOTHING IN THE DOCUMENTS SHOWING THAT THIS | | | INSTALLATION MEETS CHAPTER 11 SECTION 1102 OF THE FBC M | | | FOR REFRIGERATION. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|