2021-06-02 09:12:181ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21051117
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PRIVATE PROVIDER MUST SUBMIT REQUIRED DOCUMENTS FOR
 THIS PROJECT.
  
 2) THE WALK-IN COOLER REFRIGERATION AND THE WALK-IN
 COOLER SPEC SHEETS DO NOT HAVE THE JOB INFORMATION
 FILLED IN, PLEASE COMPLETE THIS AS WE MUST HAVE THE JOB
 INFORMATION TO SEE IT IS SITE SPECIFIC. FBC 107.2.1
  
 3) THE PRIVATE PROVIDER DID NOT STAMP THE DRAWING.
 PRIVATE PROVIDER MUST REVIEW AND APPROVE THIS PROJECT
 BEFORE THE PROJECT IS SUBMITTED TO THE CITY OF WEST
 PALM BEACH.
  
 4) THERE IS NOTHING IN THE DOCUMENTS SHOWING THAT THIS
 INSTALLATION MEETS CHAPTER 11 SECTION 1102 OF THE FBC M
 FOR REFRIGERATION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  