Plan Review Notes
Plan Review Notes For Permit 21051109
Permit Number 21051109
Review Stop P
Sequence Number 1
Notes
Date Text
2021-05-28 11:08:3505/28/21 1ST POOL PLUMBING REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1. PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PUMP, GAS HEATER CHANNEL DRAIN, CARTRIDGE FILTER AND
 SALT SYSTEM PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 2. PLEASE INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS
 FOR THE PUMP BEING INSTALLED ON THIS SYSTEM PER THE WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 3. PLEASE SUBMIT DOCUMENTATION THAT THE GAS POOL HEATER
 MEETS THE MINIMUM REQUIRED EFFICIENCY AND SHALL HAVE A
 MINIMUM THERMAL EFFICIENCY OF 82% BY THE 2020
 FBC-ENERGY SEC.R403.10.4
  
 4. HEATED SWIMMING POOLS AND IN GROUND PERMANENTLY
 INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT
 COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR
 OTHER MEANS PROVEN TO REDUCE HEAT LOSS AND A SOLAR
 COVER REQUIRED FOR GAS HEATER PER 2020 FBC RE 403.10.3.
  
 5. A CONTAINMENT REDUCED PRINCIPAL ZONE BACKFLOW DEVICE
 WILL BE REQUIRED AT THE WATER METER BY A LICENSED
 CONTRACTOR WITH A SEPARATE PERMIT AND CERTIFIED BY THE
 CITY OF WEST PALM BEACH UTILITY DEPARTMENT PER THE
 CROSS CONNECTION CONTROL MANUAL PAGE 11 (C). THIS IS
 DUE TO THE AUTOFILL ON THE POOL, WHICH WILL REQUIRE A
 BACKFLOW DEVICE (P.V.B. ISOLATION), AND IT WILL BE
 REQUIRED TO BE CERTIFIED BY A LICENSED BACKFLOW
 CONTRACTOR. A REPORT MUST BE FILLED OUT FOR THE P.V.B.
 AND WILL NEED TO BE WITH THE PERMIT AT THE FINAL. THE
 INSPECTOR WILL TAKE THE CERTIFICATION FOR CITY RECORDS.
 THESE TWO BACKFLOWS CAN BE COMBINED IN THE SAME PERMIT.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  