Plan Review Notes
Plan Review Notes For Permit 21051017
Permit Number 21051017
Review Stop B
Sequence Number 1
Notes
Date Text
2021-06-21 16:01:16PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 1&2 FAMILY - SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: SURVEY GENERATOR TO BUILDING SEPERATION
  
  
 1) SURVEY: CORRECT THE 5 FT. GENERATOR EXHAUST
 CLEARANCE TO OPENINGS INTO THE BUILDING. A 10 FT.
 CLEARANCE IS REQUIRED TO MECHANICAL AND GRAVITY AIR
 INTAKES INTO THE BUILDING PER SECTION R303.5.1 FBC RES.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  