| 2021-06-23 09:45:26 | COMPLETE GAS PLANS TO BE SUBMITTED UNDER SEPARATE |
| | PERMIT PER NOTE ON PERMIT APPLICATION. |
| | REQUIRED PLANS AND SPECS LISTED BELOW. |
| | |
| | PERMIT- 21051013 |
| | 6/23/2021 |
| | |
| | 1) PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES |
| | THE PIPING TO THE NEW GENERATOR AND ALL EXISTING GAS |
| | PIPING AND APPLIANCES AT THE RESIDENCE- SECTION G2412.3 |
| | & G2412.4 FBC RES. REFER TO FBC RES. CHAPTER 24 FUEL |
| | GAS- THE RISER SHALL INDICATE: |
| | A) TYPE OF GAS- NATURAL OR LP. |
| | B) DELIVERY PRESSURE AT THE METER. |
| | C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| | D) TYPES AND SIZES OF PIPING. |
| | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE |
| | UNIONS. |
| | H) OUTLET PRESSURES AT REGULATORS. |
| | I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| | K) PIPE SIZING TABLES. |
| | |
| | 2) SUBMIT CUT SHEETS FOR ALL EQUIPMENT RELATING TO THE |
| | GAS INSTALLATION SUCH AS REGULATORS, AND THE GENERATOR |
| | FLEX CONNECTOR- SECTIONS G2421.2 & G2422.1.2 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |