| Plan Review Notes For Permit 21050942 |
| Permit Number |
21050942 |
|
| Review Stop |
Z |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-12-06 17:12:06 | FAILED | | | | | | STROREFRONT TYPE 3 - SIGN TYPE 1A FASCIA IDENTITY SIGN | | | | | | 1) REPEAT COMMENT: THE SCOPE OF WORK INDICATES ONLY A | | | PORTION OF THE SIGN IS BEING REPLACED, BUT STAFF IS | | | UNABLE TO DETERMINE WHAT THAT IS BY THE DRAWING | | | PROVIDED. THE EXISTING SIGN DOES NOT CONFORM TO THE | | | ROSEMARY SQUARE MASTER SIGN PLAN, SO IF THE ENTIRE SIGN | | | IS REMOVED, THEN IT MUST BE REPLACED IN CONFORMANCE | | | WITH THE CURRENT SIGNAGE REGULATIONS, WHICH DOES NOT | | | OCCUR WITH THE SIGN AS PROPOSED. THE PLANS MUST CLEARLY | | | INDICATE WHAT IS BEING REPLACED AND WHAT IS REMAINING. | | | | | | 2) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN | | | CRITERIA REQUIRE THAT ALL CONDUIT, CROSSOVERS, JBOXES, | | | BELL BOXES, AND WIRING NECESSARY FOR THE SIGN'S | | | ELECTRICAL CONNECTION TO BE CONCEALED AND NOT VISIBLE | | | TO THE PUBLIC. THE PLANS STATE THAT THERE WILL BE A NEW | | | LED LIGHTING SYSTEM. PROVIDE DETAILS TO VERIFY THAT THE | | | NEW LIGHTING SYSTEM IS NOT VISIBLE TO THE PUBLIC. THIS | | | INCLUDES THE ELECTRICAL AT THE SIGN TO THE POWER SUPPLY | | | AT THE BUILDING. | | | | | | THE COMMENTS ABOVE WERE ADDRESSED ON THE OTHER PERMITS | | | THROUGH THE SUBMITTAL OF THE ENGINEER DRAWING; HOWEVER, | | | THE ENGINEER PLAN WAS NOT UPLOADED WITH THIS CURRENT | | | PERMIT. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | |
|