Plan Review Notes
Plan Review Notes For Permit 21050931
Permit Number 21050931
Review Stop E
Sequence Number 1
Notes
Date Text
2021-05-21 15:31:23PROVISO: FEEDER FROM EXISTING PANEL TO POOL PANEL IS
 PROTECTED BY A 2P - 80 AMPS BREAKER AND CONDUCTOR SIZE
 IS SHOWN AS 2#6 CU BUT IT MUSTBE #4 CU MINIMUM. SEE
 NOTE ON DRAWING. EQ
  
  