| 2021-10-29 15:54:37 | RESIDENTIAL(R3) ADDITION/ALTERATION, SECOND BUILDING |
| | REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21050921 |
| | |
| | NOTE: SEC. 606 AND SEC. 1101.1 FBC-EXISTING BUILDING. |
| | ALL NEW WORK SHALL COMPLY WITH THE MATERIALS AND |
| | METHODS REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE. |
| | |
| | 1-OK |
| | 2-OK |
| | 3-OK |
| | |
| | ORIGINAL COMMENT: |
| | 4-PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4 |
| | FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | THERE IS A SIGNIFICANT DIFFERENCE IN THE FOOTING SIZES |
| | RECOMMENDED ON THE GEOTECHNICAL REPORT SUBMITTED AND |
| | FOOTING SIZES SPECIFIED ON THE STRUCTURAL PLANS. |
| | ENGINEER OF RECORD TO ADDRESS THIS ISSUE. ENGINEER TO |
| | ACKNOWLEDGE REVIEW OF GEOTECHNICAL REPORT AND RESPOND |
| | TO THE REPORT RECOMMENDATIONS. REVISE FOOTING AS |
| | REQUIRED. SEC. 107.2.1.2 CITY AMENDMENTS. |
| | NOTE: FOOTINGS NEED GO BE AT LEAST 12 INCHES BELOW |
| | GRADE. BASED ON THE EXTERIOR ELEVATIONS IT LOOKS LIKE |
| | THE EXISTING HOUSE IS RAISED ABOVE FINISHED GRADE. IT |
| | LOOKS LIKE THE DEPTH OF THE FOOTING NEEDS TO BE REVISED |
| | TO MEET THE GEOTECHNICAL REPORT RECOMMENDATIONS AND THE |
| | 12 INCHES BELOW FINISHED GRADE REQUIREMENT. |
| | |
| | ORIGINAL COMMENT: |
| | 5- NEW FRONT BEDROOM ON SHEET A.1: |
| | EGRESS WINDOW #3 DOESN'T COMPLY WITH THE MINIMUM CLEAR |
| | HEIGHT OPENING REQUIRED BY SEC. R310.2.1 |
| | FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. WINDOW SIZE WAS NOT REVISED. SINGLE |
| | HUNG WINDOW 4'-4"WIDE BY 4'-10" HIGH DOESN'T PROVIDE |
| | THE 24" CLEAR HEIGHT OPENING. REVISE AS REQUIRED (SEE |
| | MANUFACTURER'S CATALOGS FOR EGRESS WINDOWS PROPER SIZE) |
| | OR PROVIDE MANUFACTURER'S CUT SHEET SHOWING THAT 4'-10" |
| | HIGH SINGLE HUNG WINDOW MEETS THE CLEAR HEIGHT |
| | REQUIREMENT. |
| | NOTE: IF INSTALLING IMPACT WINDOWS, THEN TAKE INTO |
| | CONSIDERATION THAT THEY REQUIRE BIGGER FRAMES. |
| | |
| | 6- OK |
| | |
| | 7- DEFERRED SUBMITTAL: |
| | A)EXTERIOR DOORS AS SHOWN ON PLANS. |
| | B)WINDOWS AS SHOWN ON PLANS. |
| | C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE |
| | TO AVOID DELAYS/CONFLICTS). |
| | C)SHUTTERS AND, PROVIDE COMPLETE INSTALLATION SCHEDULE. |
| | SEE CITY SAMPLE. |
| | D)ROOF SHINGLES. |
| | |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |