| 2021-07-12 17:15:17 | PLAN REVIEW ROOFING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2017 NEC |
| | |
| | 2ND REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | NOTICE: COMMENTS FROM 1ST REVIEW HAVE NOT BEEN |
| | ADDRESSED. SEE BELOW. |
| | |
| | 1. ROOFING PERMIT REQUIRED. |
| | PERMITS - 105.1 REQUIRED. |
| | |
| | 2. NOA SUBMITTED FOR ROOFING INCLUDES PAGE 1 ONLY. |
| | PROVIDE COMPLETE SET OF PRODUCT APPROVALS |
| | |
| | 3. PROVIDE PRODUCT APPROVALS FOR UNDERLAYMENT. |
| | |
| | R905.1.1UNDERLAYMENT. |
| | UNDERLAYMENT FOR ROOF SLOPES 2:12 AND GREATER SHALL |
| | CONFORM TO THE APPLICABLE STANDARDS LISTED IN THIS |
| | CHAPTER. UNDERLAYMENT MATERIALS REQUIRED TO COMPLY WITH |
| | ASTM D226, D1970, D4869 AND D6757 SHALL BEAR A LABEL |
| | INDICATING COMPLIANCE TO THE STANDARD DESIGNATION AND, |
| | IF APPLICABLE, TYPE CLASSIFICATION INDICATED. |
| | UNDERLAYMENT FOR ROOF SLOPES 2:12 AND GREATER SHALL BE |
| | APPLIED AND ATTACHED IN ACCORDANCE WITH SECTION |
| | R905.1.1.1, R905.1.1.2 OR R905.1.1.3, AS APPLICABLE. |
| | |
| | R905.1.1.2UNDERLAYMENT FOR CONCRETE AND CLAY TILE. |
| | UNDERLAYMENT FOR CONCRETE AND CLAY TILE SHALL COMPLY |
| | WITH SECTION 905.3.3. |
| | |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. |
| | |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |