| 2021-07-01 13:34:35 | AUDIT |
| | RESIDENTIAL(R2) ALTERATION . |
| | PERMIT #21050878 |
| | |
| | 1- PLANS SHOW REMOVAL OF DRYWALL AND INSTALLATION OF |
| | TOWEL BAR IN THE EXISTING SHAFT: |
| | A)PLANS DON'T PROVIDE INFORMATION SHOWING HOW THE FIRE |
| | RATING INTEGRITY OF THE CHASE IS GOING TO BE KEPT. |
| | THERE ARE NO DETAILS/SPECIFICATIONS OF APPROVED FIRE |
| | RATED CHASE ASSEMBLY. PROVIDE DETAILS/SPECIFICATIONS OF |
| | APPROVED EXISTING ASSEMBLY. AND, PROVIDE COMPLETE |
| | DETAILS/SPECIFICATIONS OF APPROVED RETROFIT ASSEMBLY. |
| | SEC. 801.3 FBC-EXISTING BUILDING. SEC. 713 |
| | FBC-BUILDING. |
| | |
| | B)PLANS DON'T PROVIDE INFORMATION SHOWING PENETRATION |
| | PROTECTION AS REQUIRED BY SEC. 713.8.2 FBC-BUILDING. |
| | SEC. 801.3 FBC-EXISTING BUILDING. |
| | |
| | 2- PLANS DON'T PROVIDE INFORMATION FOR THE FLOORING |
| | UNDERLAYMENT. SEE REQUIRED INFORMATION BELOW. |
| | SEC. 801.3 FBC-EXISTING BUILDING. |
| | SEC. 720.1 OF FBC 7TH EDITION (2020). |
| | SEC. 1207.2 OF FBC 7TH EDITION (2020). |
| | SEC. 1207.3 OF FBC 7TH EDITION (2020). |
| | |
| | FLOORING SOUND INSULATION MATERIAL: |
| | A) PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE |
| | DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION |
| | (2020). |
| | |
| | B) PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC) |
| | TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY |
| | SEC. 1207.2 OF FBC 7TH EDITION (2020). |
| | |
| | C) PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC) |
| | TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY |
| | SEC. 1207.3 OF FBC 7TH EDITION (2020). |
| | |
| | NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING |
| | CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE |
| | TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT |
| | ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED |
| | ACOUSTICAL CEILINGS IN THESE BUILDINGS. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |