Plan Review Notes
Plan Review Notes For Permit 21050854
Permit Number 21050854
Review Stop SIGNATURE
Sequence Number 3
Notes
Date Text
2022-01-04 14:08:53THE GENERATOR PAD ENGINEERING DOES NOT HAVE THE
 ENGINEER'S DIGITAL SIGNATURE ON IT. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT
 OR ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 481 & 61G1 OR FS 471 & 61G15
 NOTE: THE PAD DRAWINGS THAT WERE SUBMITTED ARE NOT FOR
 THE CUMMINS RS30 GENERATOR. THE GENERATOR IS 94" LONG
 AND THE PAD IS ONLY 54" LONG. SUBMIT A SIGNED AND
 SEALED PAD DRAWING THAT IS FOR THE CUMMINS RS 30
 GENERATOR.