| 2022-01-04 14:08:53 | THE GENERATOR PAD ENGINEERING DOES NOT HAVE THE | | | ENGINEER'S DIGITAL SIGNATURE ON IT. ELECTRONICALLY | | | SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT | | | OR ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE | | | THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER | | | VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE | | | BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER | | | DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE | | | ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE | | | AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO | | | PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE | | | ACCEPTABLE. FS 481 & 61G1 OR FS 471 & 61G15 | | | NOTE: THE PAD DRAWINGS THAT WERE SUBMITTED ARE NOT FOR | | | THE CUMMINS RS30 GENERATOR. THE GENERATOR IS 94" LONG | | | AND THE PAD IS ONLY 54" LONG. SUBMIT A SIGNED AND | | | SEALED PAD DRAWING THAT IS FOR THE CUMMINS RS 30 | | | GENERATOR. |
|