Plan Review Notes
Plan Review Notes For Permit 21050854
Permit Number 21050854
Review Stop B
Sequence Number 1
Notes
Date Text
2021-10-13 10:21:05BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: WORK DESCRIPTION STATES "REPLACE EXACT SIZE
 GENERATOR". CITY RECORDS SHOW THE EXISTING GENERATOR IS
 A 20KW UNIT. REPLACEMENT GENERATOR IS A 30KW UNIT.
 ALSO, THE LOCATION IS DIFFERENT THAN THE EXISTING UNIT.
  
 1. PROVIDE A STRUCTURAL SLAB WITH ATTACHMENT DETAIL.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PROVIDE DESIGN WIND LOADS FOR PROPOSED GENERATOR.
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
  
  
  