| Plan Review Notes For Permit 21050816 |
| Permit Number |
21050816 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-06-25 10:48:54 | 2ND REVIEW FBC-2020 MECHANICAL | | | PERMIT-21050816 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M6.1: THE OUTDOOR AIR CALCULATIONS CHART | | | INDICATES IT IS BASED ON THE FLORIDA MECHANICAL CODE | | | 2020, TABLE 403.3.1.1 BUT NOTE 1 INDICATES CALCULATIONS | | | ARE BASED ON ARCHITECTURAL PLANS AND ASHRAE 62.1-16. | | | PLEASE CHOSE WHICH METHOD THAT WILL BE USED AND PROVIDE | | | THE CALCULATIONS BASED ON THAT METHOD. IF ASHRAE IS | | | USED IT MUST BE USED FOR THE ENTIRE MECHANICAL SYSTEM. | | | IT CANNOT BE USED JUST FOR THE VENTILATION | | | CALCULATIONS. FBC M 403.2 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|