Plan Review Notes
Plan Review Notes For Permit 21050816
Permit Number 21050816
Review Stop M
Sequence Number 2
Notes
Date Text
2021-06-25 10:48:542ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21050816
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M6.1: THE OUTDOOR AIR CALCULATIONS CHART
 INDICATES IT IS BASED ON THE FLORIDA MECHANICAL CODE
 2020, TABLE 403.3.1.1 BUT NOTE 1 INDICATES CALCULATIONS
 ARE BASED ON ARCHITECTURAL PLANS AND ASHRAE 62.1-16.
 PLEASE CHOSE WHICH METHOD THAT WILL BE USED AND PROVIDE
 THE CALCULATIONS BASED ON THAT METHOD. IF ASHRAE IS
 USED IT MUST BE USED FOR THE ENTIRE MECHANICAL SYSTEM.
 IT CANNOT BE USED JUST FOR THE VENTILATION
 CALCULATIONS. FBC M 403.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  