| 2021-06-26 11:58:29 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1) MEETING ROOM/ CONFERENCE ROOM SHALL MEET THE | | | REQUIREMENTS OF 210.71. | | | | | | 210.71(B)(2) FLOOR RECEPTACLE OUTLETS. A MEETING ROOM | | | THAT IS AT LEAST 3.7 M (12 FT) WIDE AND THAT HAS A | | | FLOOR AREA OF AT LEAST 20 M2 (215 FT2) SHALL HAVE AT | | | LEAST ONE RECEPTACLE OUTLET LOCATED IN THE FLOOR AT A | | | DISTANCE NOT LESS THAN 1.8 M (6 FT) FROM ANY FIXED WALL | | | FOR EACH 20 M2 (215 FT2) OR MAJOR PORTION OF FLOOR | | | SPACE. | | | | | | 2) OUTLETS IN KITCHEN TO BE GFI PROTECTED WHEN WITHIN | | | 6" OF THE SINK. 210.8(B)(5) |
|