| 2021-06-16 14:47:11 | OFFICE ALTERATION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) CODE USED FOR DESIGN SHOULD BE THE CODE IN EFFECT | | | (2020 FBC) | | | 2) PLEASE SHOW THE HOURLY FIRE RATING FOR THE DOORS AND | | | THE GLAZING IN THE DOORS (800 AND 829) FROM THE OFFICES | | | TO THE EGRESS CORRIDOR FBC 716 - OR SHOW HOW THE | | | ELEVATOR IS PROTECTED FBC 3006.2 | | | 3) PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE SINK AND | | | APPLIANCES IN THE BREAK ROOM TO COMPLY WITH FBC | | | ACCESSIBILITY 305 | | | 4) PLEASE SHOW THE REACH RANGE FOR THE MICROWAVE OVEN | | | TO COMPLY WITH FBC ACCESSIBILITY 308 | | | | | | |
|