Plan Review Notes
Plan Review Notes For Permit 21050808
Permit Number 21050808
Review Stop B
Sequence Number 2
Notes
Date Text
2021-09-01 18:20:40RESIDENTIAL (R3) ROOFING SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21050808
  
 1- ITEM #1 AND #3 FROM PREVIOUS PLAN REVIEWER ARE OK.
  
 2- ITEM #2 FROM PREVIOUS PLAN REVIEWER NEEDS TO BE
 ADDRESSED.
 A) NEW MODIFIED BITUMEN ROOF SYSTEM SUBMITTED
 FL1654-R23 IS OLD AND IT IS FOR THE PREVIOUS 2017 CODE.
 NEED CURRENT PRODUCT APPROVAL FOR 2020 CODE.
  
 B)SELECTED ASSEMBLY ON PAGE 19 OF 65 IS NOT CLEAR.
 SELECTED ASSEMBLY READS W-01 AND THE MAXIMUM DESIGN
 PRESSURE READS 12.5. CLARIFY/REVISE AS REQUIRED. AND
 NEED CURRENT PRODUCT APPROVAL. SEE ITEM 2(A) ABOVE.
 SELECT ASSEMBLY THAT MEETS THE DESIGN PRESSURES FOR ALL
 ROOF ZONES OR ENGINEERING WILL BE REQUIRED.
  
 3- CLARIFY SHINGLES ROOF UNDERLAYMENT AS REQUIRED BY
 SEC. R905.1.1.1. FBC-RESIDENTIAL. INSTALLING TWO LAYERS
 OF 30# FELT?
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
 *******************************************
  
  
 COPY OF COMMENTS FROM PREVIOUS PLANS EXAMINER.
  
 JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC B 107.2.1. CITY OF WEST PALM BEACH IS NOT
 LOCATED IN A HVHZ AND HAS NOT ADOPTED RAS 128.
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL2533-R25 SELECTED SYSTEM NO. W-103 DO NOT
 MEET THE EXPOSURE CATEGORY C; ZONE 3 MINIMUM DESIGN
 PRESSURE REQUIREMENT OF -108.17. PLEASE SELECT SYSTEM
 NO. THAT MEETS OR EXCEEDS REQUIREMENTS OR PROVIDE
 SIGNED AND SEALED ENGINEERED NAILING CALCULATION FOR
 ZONE 3. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE
 CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN
 PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 3. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED RIDGE VENT SYSTEM TO
 BE USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
  
  
  
  
  
  