| 2021-06-03 07:51:02 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21050803 |
| | 6/3/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A1: PLEASE PROVIDE THE CLEAR FLOOR SPACE |
| | DIAGRAMS AND DIMENSIONS FOR THE WATER CLOSET AND |
| | LAVATORY IN THE WTR- SECTIONS 604.3 & 606.2 FBC ACC. |
| | |
| | 2) P1: THE DRINKING FOUNTAIN DRAIN CANNOT CONNECT TO |
| | THE TOILET ROOM WET VENT- SECTION 912.1 FBC P. THE DF |
| | DRAIN SHALL DISCHARGE DOWNSTREAM OF THE WET VENT. |
| | |
| | 3) P1: REFER TO SECTIONS C404.5.1 & C404.5.2 FBC EC: |
| | THE PIPING RUNS FROM THE NEW WATER HEATER TO THE |
| | LAVATORIES IS EXCEEDING THE MAXIMUM ALLOWABLE 2 FT. |
| | LENGTH. PLEASE RELOCATE THE WATER HEATER OR PROVIDE A |
| | RECIRCULATION PUMP. |
| | |
| | 4) P1: INDICATE HOW TEMPERED WATER WILL BE PROVIDE TO |
| | THE LAVATORIES- SECTIONS 419.5 & 607.2.1 FBC P. |
| | |
| | 5) P1: PROVIDE HW PIPE INSULATION SPECIFICATIONS- TABLE |
| | C403.3.10 FBC EC. |
| | |
| | 6) A1: REFER TO SECTION 310.3 FBC P AND SECTION |
| | 1210.2.2 WALLS AND PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, |
| | URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| | NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4 |
| | FEET ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL |
| | ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF |
| | A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| | PLEASE NOTE THAT EPOXY PAINTED DRYWALL DOES NOT MEET |
| | COMPLIANCE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |