2021-06-10 16:57:06CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1.PLUMBING NOTES REFER TO 2017 FBC. PER WPB FBC
 107.2.1, ALL FLORIDA BUILDING CODE REFERENCES SHALL BE
 2020, 7TH EDITION.
  
 2.PROVIDE SCHEDULE; MANUFACTURER, MODEL #, CAPACITY
 (GPM FOR TANKLESS), ELECTRICAL OR GAS CHARACTERISTICS.
 SHOW THAT IT IS RATED FOR OUTDOOR USE. IF GAS, A GAS
 PERMIT WILL BE REQUIRED AND PLANS SUBMITTED.
  
 3.PER WPB FBC 107.2.1, PROVIDE DETAIL OF TANKLESS WATER
 HEATER SHOWING ALL REQUIRED CONNECTIONS, SAFETY DEVICES
 AND VALVES.
  
 4.WET BAR; SINK; THE VENT SHALL CONNECT ABOVE THE TRAP
 WEIR OF THE FIXTURE AND RISE VERTICALLY TO 6 INCHES
 ABOVE THE FLOOD LEVEL RIM OF THE FIXTURE BEFORE
 OFFSETTING HORIZONTALLY. FBC RES P3104.4, P3105.1 AND
 P3201.5. ADDITIONALLY, THE VENT AS SHOWN IS 3 INCH
 CONNECTED TO 2 INCH. CLARIFY.
  
 5. PER WPB FBC 107.2.1, CORRECTLY IDENTIFY THE SINK
 (WET BAR) ON THE RISER DIAGRAM. IT IS NOT A LAVATORY.
  
 6.RE: 3 INCH VENT AT INFILLED WINDOW AT BATHROOM #2;
 THIS APPEARS TO BE IN A BEARING BLOCK WALL. PER WPB FBC
 107.2.1, PROVIDE DETAIL SHOWING HOW VENT SHALL
 PENETRATE EXISTING BEAM(S) OR OFFSET AROUND SAID
 BEAM(S).
  
 NOTE; REVIEW VENT SIZES. FBC RES DOES NOT REQUIRE 3
 INCH VENTS ON THIS PROJECT AND THEY MAY STRUCTURALLY
 IMPACT THE WALLS/PARTITIONS AND BEAMS.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 PLEASE CALL 561-246-0882 WITH ANY QUESTIONS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21050800 520 HAMPTON RD