| 2021-11-12 07:14:42 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 4TH REVIEW |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | FOURTH REQUEST: PER WPB FBC 107.2.1, PROVIDE A SHOWER |
| | WALL/ LINER/THRESHOLD DETAIL SHOWING THE FOLLOWING |
| | INFORMATION SHOWING COMPLIANCE WITH FBC PL 421. |
| | |
| | PARTIALLY COMPLIED;SEE BELOW |
| | |
| | 1.DETAIL SHALL INCLUDE ALL COMPONENTS OF FBC PL 421.5.2 |
| | AS FOLLOWS: |
| | LINERS SHALL TURN UP ON ALL SIDES NOT LESS THAN 2 |
| | INCHES ABOVE THE FINISHED THRESHOLD LEVEL |
| | LINERS SHALL BE RECESSED AND FASTENED TO AN APPROVED |
| | BACKING |
| | LINERS SHALL NOT BE NAILED OR PERFORATED AT ANY POINT |
| | LESS THAN 1 INCH ABOVE THE FINISHED THRESHOLD |
| | LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12 |
| | UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE SLOPED |
| | TOWARD THE FIXTURE DRAIN |
| | LINERS SHALL BE SECURELY FASTENED TO THE WASTE OUTLET |
| | AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT JOINT |
| | BETWEEN THE LINER AND THE OUTLET |
| | FLOORS OR RECEPTORS UNDER SHOWER COMPARTMENTS SHALL BE |
| | LAID ON, AND SUPPORTED BY, A SMOOTH AND STRUCTURALLY |
| | SOUND BASE. |
| | |
| | 2. LINER MATERIAL (SPECIFY LINER MATERIAL COMPLYING |
| | WITH ONE OF THE FOLLOWING FBC PL SECTIONS-421.5.2.1, |
| | 421.5.2.2, 421.5.2.3, 421.5.2.4, 421.5.2.5 OR |
| | 421.5.2.6.) NOTE THAT FBC PL 421.5.2.1 PLASTICIZED |
| | POLYVINYL CHLORIDE (PVC) SHEETS MEETING THE |
| | REQUIREMENTS OF ASTM D4551 IS A COMMON LINER USED. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |
| | 21050792 400 N FLAGLER DR # 1705 |
| | |
| | |