2021-06-16 11:29:09BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) ON DRAWING A-4.1 - ACCESSIBLE FITTING ROOM - PLEASE
 SHOW THE BENCH SEAT TRANSFER CLEAR FLOOR SPACE BESIDE
 THE BENCH PER FBC ACCESSIBILITY 903.2
 2) ON DRAWING A-4.1 - ACCESSIBLE FITTING ROOM - PLEASE
 SHOW THE DOOR CLEAR FLOOR SPACE TO EXIT THE ACCESSIBLE
 FITTING ROOM FBC ACCESSIBILITY 404.2.4 (18" BESIDE THE
 DOOR LATCH SIDE)
 3) ON DRAWING A-4.1 - ACCESSIBLE FITTING ROOM - PLEASE
 SHOW THE CLEAR FLOOR SPACE PER FBC ACCESSIBILITY 803.3
 DOOR SWING. DOORS SHALL NOT SWING INTO THE ROOM UNLESS
 A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305.3 IS
 PROVIDED BEYOND THE ARC OF THE DOOR SWING.
 4) PLEASE SHOW THE HOURLY FIRE RATING FOR THE EXISTING
 TENNANT SEPARATION WALLS FBC 508
 5) BUILDING OCCUPANT LOAD AND THE EGRESS WIDTH DO NOT
 MATCH PER CALCULATIONS (198 X .02) - SHOWN ON DRAWING A
 0.1 FBC 1005.3.2
  