| Date |
Text |
| 2021-05-27 16:30:34 | 05/27/21 1ST GAS/LP/TANK REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | THERE IS NO SCOPE OF WORK, AND NOT CLEAR WHO IS GOING |
| | TO INSTALL THE APPLIANCES. PLEASE PROVIDE THE |
| | INFORMATION BELOW OR CLARIFY WHO WILL BE DOING THE |
| | WORK. |
| | |
| | 1. GAS RISER DIAGRAM REQUIRED PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS. |
| | |
| | 2. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2020 FBC RES. |
| | SECS. G2413.4.1, G2413.4.2. |
| | |
| | 3. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. INDICATE THE SYSTEM'S DELIVERY PRESSURE (PSI) ON THE |
| | PLAN PER THE 2020 FBC FG SEC. 402.2 OR 2017 FBC RES. |
| | SEC. G2413.2. |
| | |
| | 5. PLEASE PROVIDE THE TOTAL DISTANCE FROM THE POINT OF |
| | DELIVERY (GAS METER / MP REGULATOR / LP TANK) TO THE |
| | MOST REMOTE OUTLET OF THE SYSTEM PER THE 2020 FBC RES. |
| | SEC. G2413.4.1. |
| | |
| | 6. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| | THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| | STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.1 GENERAL. |
| | |
| | 7. PLEASE SHOW AND LABEL DRIP LEG ON EQUIPMENT |
| | INSTALLED, EXCEPT FOR RANGE PER THE 2020 FBC RES. SEC. |
| | G2419.2. |
| | |
| | 8. ON HOUSE PLAN SHOWING THE LOCATION OF THE TANK-LESS |
| | WATER HEATER AND THE LOCATION AND DISTANCE OF ANY |
| | OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER |
| | HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY |
| | WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 9. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2020 |
| | FBC RES. SEC. G2407.1 AND G2439.4 (CLOTHES DRYERS). IF |
| | LOUVER USED, PLEASE SHOW THE LOUVER(S) SIZE ON THE |
| | PLANS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 10. SUBMIT MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1. |
| | |
| | 11. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE FBC |
| | RES. SEC. G2413.2 AND G2404.3. |
| | |
| | 12. PLEASE PROVIDE A HOUSE PLAN SHOWING THE LOCATION OF |
| | THE TANK-LESS WATER HEATER AND THE LOCATION AND |
| | DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION |
| | TO THE WATER HEATER. THE LOCATION OF THE WATER HEATER |
| | SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 13. PIPES OUTSIDE NEED TO BE INSULATED WITH A MINIMUM |
| | R-3 PER THE 2020 FBC SEC. RE 403.5.3. |
| | |
| | 14. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS |
| | ABOVE GROUND OR BELOW GROUND, AND SHOW THE METHOD OF |
| | REQUIRED PROTECTION FOR THE LP TANK AND APPURTENANCES |
| | PER NFPA 58. FOR EXAMPLE, IF THE TANK IS BELOW GROUND, |
| | IT SHALL BE ANCHORED PER NFPA 58 SEC.3-2.2.7 (H). IF |
| | ABOVE GROUND, THE TANK SHALL BE SECURELY ANCHORED TO |
| | WITHSTAND 170 MPH ULT WIND LOAD PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 15. CLEARLY INDICATE ON THE TIE-DOWN SHEET IF THE LP |
| | TANK TIE-DOWN METHOD AND IF YOU ARE USING STRAPS OR |
| | CABLE, IF CABLE HOW IS IT PROTECTED FOR THE LP TANK AND |
| | APPURTENANCES PER NFPA 58 AND WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 16. PROVIDE THE SIZE OF THE HOLD-DOWN CABLES/STRAPS FOR |
| | THE TANK AND THE TYPE AND LENGTH OF GROUND ANCHORS TO |
| | BE INSTALLED TO PREVENT FLOTATION PER THE NFPA 58 SEC. |
| | 6.6.1.6. |
| | |
| | 17. SUBMIT DETAILS ON THE TYPE OF CATHODIC PROTECTION, |
| | SIZE (LBS.) & THE NUMBER OF MAGNESIUM BAG(S), SIZE & |
| | TYPE OF ANODE CABLE AMOUNT OF WATER TO ACTIVATE IT PER |
| | THE NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I). |
| | |
| | 18. PLEASE PROVIDE THE DEPTH OF THE CONTAINER BELOW |
| | GRADE. COMPLY WITH THE NFPA 58 SEC. 6.6.6.1. |
| | |
| | 19. PIPES NOT IN CONDITION SPACE NEED TO BE INSULATED |
| | WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE 403.5.3, |
| | PLEASE NOTE ON PLANS. |
| | |
| | 20. IF THE TANK-LESS UNIT HAS CONDENSATE, IT WILL NEED |
| | TO BE 1' AWAY FROM THE STRUCTURE PER THE 2020 FBC SEC. |
| | R318.5, PLEASE NOTE ON PLANS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |