| Plan Review Notes For Permit 21050743 |
| Permit Number |
21050743 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-06-02 13:28:47 | PLAN REVIEW BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER PX3169 1&2 FAMILY - SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | RE: BUILDING MRH IS 80 FEET. | | | | | | 1. PROVIDE SITE SPECIFIC DESIGN WIND LOADS PER FBC CHPT | | | 16 AND ASCE 7-16. CALCULATIONS SHALL BE PREPARED BY | | | FLORIDA LICENSED DESIGN PROFESSIONAL. | | | 1609.1.1DETERMINATION OF WIND LOADS. | | | WIND LOADS ON EVERY BUILDING OR STRUCTURE SHALL BE | | | DETERMINED IN ACCORDANCE WITH CHAPTERS 26 TO 30 OF ASCE | | | 7. WIND SHALL BE ASSUMED TO COME FROM ANY HORIZONTAL | | | DIRECTION AND WIND PRESSURES SHALL BE ASSUMED TO ACT | | | NORMAL TO THE SURFACE CONSIDERED. | | | | | | FBC 107.3.5.1.(8) PROVIDE WIND DESIGN LOADS/DESIGN | | | PRESSURES PURSUANT TO FBC-CHAPTER 16 | | | | | | 2. WINDOW AND SGD DEVICES ARE IMPACT RATED. REMOVE | | | SCHEDULE FOR OPENING PROTECTION DEVICES OR ASSEMBLIES. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | |
|