| 2021-05-25 22:00:32 | CTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. ARE YOU PROPOSING A NEW 400AMP SERVICE? OR IS THAT |
| | THE LOCATION OF THE EXISTING SERVICE? FBC 107.2.1 |
| | |
| | INFORMATIONAL NOTE: PER NEC 230.2 ONLY ONE SERVICE IS |
| | PERMITTED PER BUILDING UNLESS ONE OF THE CONDITIONS OF |
| | NEC 230.2 IS MET. |
| | |
| | 2. PROVIDE LOAD CALCULATION. NEC 215, 220 |
| | |
| | 3. PROVIDE PANEL SCHEDULES. FBC 107.2.1 |
| | |
| | 4. PROVIDE ONE-LINE DIAGRAM OF PROPOSED WORK AND |
| | SERVICE. FBC 107.2.1 |
| | |
| | 5. NO OVERCURRENT PROTECTION SHOWN FOR NEW CAR |
| | CHARGERS. FBC 107.2.1 |
| | |
| | 6. VALUE LOW FOR AMOUNT OF WORK SHOWN. PROVIDE ACCURATE |
| | VALUE AND SIGNED CONTRACT. SIGNED BY BOTH OWNER AND |
| | CONTRACTOR. FBC 109.3 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |
| | |