Plan Review Notes
Plan Review Notes For Permit 21050736
Permit Number 21050736
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-05-19 11:23:32THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS INSUFFICIENT DETAIL PROVIDED TO COMPLETE A
 REVIEW.
  
 PLEASE PROVIDE A FLOOR LAYOUT SHOWING THE LOCATION OF
 THE BATHROOM WITHIN THE UNIT.
  
  
 2) PLEASE PROVIDE DETAILS IF ANY OF THE BATHROOM WALLS
 ARE FIRE RATED SEPARATION WALLS AND A
 FIRE RATED LISTED WALL DETAIL FOR ANY REPLACEMENT
 MATERIAL ON THAT WALL
  
  
 3) PLEASE PROVIDE AN ADRESS AND UNIT NUMBER ON THE PLAN
 SHEET.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL