| Permit Number |
21050736 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-06-01 13:45:56 | BATH REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE A FLOOR PLAN SHOWING THE LOCATION OF | | | THE BATHROOM. (CAN BE HAND DRAWN) | | | 2) PLEASE SHOW THE SHOWER WALL FINISH TO COMPLY WITH | | | FBC 1210.2.3 SHOWERS. SHOWER COMPARTMENTS AND WALLS | | | ABOVE | | | BATHTUBS WITH INSTALLED SHOWER HEADS SHALL BE FINISHED | | | WITH | | | A SMOOTH, NONABSORBENT SURFACE TO A HEIGHT NOT LESS | | | THAN 72 | | | INCHES (1829 MM) ABOVE THE DRAIN INLET. | | | |
|