Plan Review Notes
Plan Review Notes For Permit 21050678
Permit Number 21050678
Review Stop M
Sequence Number 3
Notes
Date Text
2022-03-18 14:27:11PRIVATE PROVIDER MECHANICAL AUDIT
  
 CONFLICT BETWEEN ARCHITECTURAL DRAWINGS AND THE ENERGY
 CALCULATIONS:
  
 THE ENERGY CALCULATIONS DATED 2/27/2022 FROM KAREN
 OLIVER SUBMITTED IN THIS LATEST SUBMITTAL SHOWS ON PAGE
 4 OF 6 THAT MECHANICAL SYSTEM 8 IN THE GARAGE HAS 2 18
 FT BY 8 FT INSULATED GARAGE DOORS. THE MECHANICAL
 DRAWING SUBMITTED WITH THIS REVISION SHOWS 2- 9FT X 8
 FT GARAGE DOORS TO THE WEST SIDE AND 1-18 FT GARAGE
 DOOR ON THE SOUTH SIDE. THE ARCHITECTURAL DRAWINGS SHOW
 4- 9FT X 8FT DOORS TOTAL. I CALLED HILLARY MUSSER AND
 ASKED HOW MANY GARAGE DOORS WERE INSTALLED AT THIS
 LOCATION AND SHE TOLD ME THERE WERE 3 TOTAL. 2 SMALL
 DOORS AND 1 LARGE DOOR MADE TO LOOK LIKE 2. PLEASE
 PROVIDE ARCHITECTURAL/STRUCTURAL DRAWINGS TO SUPPORT
 WHAT IS ACTUALLY INSTALLED AT THIS RESIDENCE.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  