| 2021-12-16 09:42:13 | 1ST AUDIT FBC-2020 MECHANICAL |
| | PERMIT-21050678 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN AUDIT RESULTS: DENIED. |
| | |
| | 1) THE ORIGINAL APPROVED DRAWINGS DID NOT HAVE A |
| | MECHANICAL UNIT FOR THE GARAGE. THIS REVISED DRAWING |
| | SHOWS AN AHU TO DEHUMIDIFY THE GARAGE. PLEASE EITHER |
| | PROVIDE THE ENERGY CALCULATIONS AND MECHANICAL |
| | EQUIPMENT SIZING CALCULATIONS FOR THE GARAGE OR PROVIDE |
| | A HUMIDITY UNIT ONLY. FBC 107.2.1 |
| | |
| | 2) THE ORIGINAL DRAWINGS WERE DESIGNED BY ELLIS |
| | CONSULTING BEN ELLIS PE HIS DESIGN HAD 3 DRAWINGS: M-1, |
| | M-2 AND M-3. THE REVISED DRAWING FROM SMYTH AIR |
| | CONDITIONING INC. DOES NOT INCLUDE M-1. THIS SHEET, |
| | M-1, FROM THE ORIGINAL DESIGNER MR. BEN ELLIS EXPLAINS |
| | IN DETAIL ON SHEET M-1 THAT IF THERE IS A CHANGE FROM |
| | HIS ORIGINAL DESIGN IT MUST BE SENT BACK TO HIM FOR HIS |
| | APPROVAL AND STAMP. PLEASE CORRECT THIS AND SUBMIT A |
| | REVISION THAT HAS MR. ELLIS SIGNATURE ON ALL 3 SHEETS. |
| | THE MECHANICAL CONTRACTOR CAN SUBMIT EVERYTHING RELATED |
| | TO THE MECHANICAL DESIGN OF THIS PROJECT INCLUDING A |
| | NEW SHEET M-1 AND A LETTER OF INTENT TO BE THE |
| | RESPONSIBLE PARTY FOR THIS DESIGN. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |