| 2021-05-24 14:56:37 | GOLF COURSE |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) DRAWINGS NEED TO BE SIGNED AND SEALED BY THE |
| | DESIGNER - FBC WPB 107.1 IF THE DESIGN PROFESSIONAL IS |
| | AN ARCHITECT, INTERIOR DESIGNER, LANDSCAPE ARCHITECT , |
| | OR ENGINEER LEGALLY |
| | REGISTERED UNDER THE LAWS OF THIS STATE REGULATING THE |
| | PRACTICE OF ARCHITECTURE OR INTERIOR DESIGN AS |
| | PROVIDED FOR IN CHAPTER 481, FLORIDA STATUTES, PART I, |
| | OR LANDSCAPE ARCHITECTURE AS PROVIDED FOR |
| | IN CHAPTER 481, FLORIDA STATUTES, PART II, OR |
| | ENGINEERING AS PROVIDED FOR IN CHAPTER 471, |
| | FLORIDA STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| | OFFICIAL SEAL TO SAID DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA, AS REQUIRED BY |
| | FLORIDA STATUTE. |
| | |
| | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. |
| | DRAWINGS DO NOT SHOW IN "ADOBE READER" AS |
| | DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR |
| | ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR |
| | DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE |
| | ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE |
| | FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL |