| Plan Review Notes For Permit 21050675 |
| Permit Number |
21050675 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-05-19 13:37:09 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE ARE NO ADDRESS ON EACH SHEET NOR WITHIN THE | | | TITLE BLOCK OF EACH SHEET. | | | | | | PLEASE PROVIDE THE CORRECT ADDTESS WITHIN THE TITLE | | | BLOCK OF EACH SHEET | | | | | | | | | 2) THERE IS NO INDICATION OF A SEQUENCE OF OPERATION. | | | | | | THOUGH THIS IS A REPLACEMENT PANEL A SEQUENCE OF | | | OPERATION IS REQUIRED. | | | | | | PLEASE PROVIDE THE SEQUENCE OF OPERATION FOR EACH | | | APPLICABLE DEVICE. | | | | | | | | | 3) THERE IS NO VOLTAGE DROP NOR BATTERY CALCULATIONS. | | | | | | THERE IS ALSO NO INDICATION THAT THE EXISTING | | | CALCULATIONS ARE THE SAME FOR THIS NEW PANEL. | | | | | | PLEASE REVIEW AND PROVIDE THE APPLICABLE NEW | | | CLAULATIONS OR A NOTE INDICATING THEY ARE UNCHANGED. | | | | | | | | | 4) PLEASE ENSURE THAT ALL DEVICES ARE TESTED AND A | | | PROPERLY COMPLETED REORD OF COMPLETION IS PROVIDED TO | | | THE FIRE INSPECTOR ON FIRE INSPECTION. | | | | | | THE TESTING OF DEVICES WILL BE AT THE DISCRETION OF THE | | | FIRE INSPECTOR. | | | | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|