2021-06-18 16:40:26****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC R 301, ON THE INSTALLATION SCHEDULE YOU PROPOSE
 LAG SCREWS, AND ON THE PRODUCT APPROVAL YOU HAVE
 CIRCLED LAG SCREWS, BUT THAT FASTENER IS FOR WOOD
 SUBSTRATE (SEE THE NAME OF THE CHART WHERE YOU CIRCLED
 THE SPACING). YOU ALSO PROPOSE AN EDGE DISTANCE OF
 .75", THAT IS FOR WOOD. ON THE INSTALLATION SCHEDULE
 YOU STATE THAT THE SUBSTRATE IS BLOCK/CONCRETE.
  
 A COMPLETE REVIEW CANNOT BE DONE DUE TO INCONSISTENT
 INFORMATION. PROPOSED INSTALLATION IS FOR WOOD
 SUBSTRATE, INSTALLATION SCHEDULE STATES ITS
 BLOCK/CONCRETE. REVISE INSTALLATION SCHEDULE.