| Plan Review Notes For Permit 21050674 |
| Permit Number |
21050674 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-06-18 16:40:26 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC R 301, ON THE INSTALLATION SCHEDULE YOU PROPOSE | | | LAG SCREWS, AND ON THE PRODUCT APPROVAL YOU HAVE | | | CIRCLED LAG SCREWS, BUT THAT FASTENER IS FOR WOOD | | | SUBSTRATE (SEE THE NAME OF THE CHART WHERE YOU CIRCLED | | | THE SPACING). YOU ALSO PROPOSE AN EDGE DISTANCE OF | | | .75", THAT IS FOR WOOD. ON THE INSTALLATION SCHEDULE | | | YOU STATE THAT THE SUBSTRATE IS BLOCK/CONCRETE. | | | | | | A COMPLETE REVIEW CANNOT BE DONE DUE TO INCONSISTENT | | | INFORMATION. PROPOSED INSTALLATION IS FOR WOOD | | | SUBSTRATE, INSTALLATION SCHEDULE STATES ITS | | | BLOCK/CONCRETE. REVISE INSTALLATION SCHEDULE. |
|