| 2021-10-19 11:23:15 | 3RD REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21050671 |
| | 6/29/21 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS 3.0P & 3.1P: 3RD REQUEST- A MASTER |
| | THERMOSTATIC MIXING VALVE IS SPECIFIED TO PROVIDE |
| | TEMPERED WATER AT 108 DEGREES F TO ALL FIXTURES EXCEPT |
| | THE MOP SINK AND 3-COMPARTMENT, HOWEVER THE PLAN AND |
| | WATER RISER EACH SHOW HOT WATER LINES AT 140 AND 110 |
| | DEGREES F BEING. PLEASE SEE SECTION 202 FOR DEFINITIONS |
| | OF HOT AND TEMPERED WATER AND CORRECT THE PLAN. PLEASE |
| | NOTE THAT THE TEMPERED WATER IS ONLY REQUIRED FOR THE |
| | LAVATORIES REQUIRED FOR THE LAVATORIES- SECTION 419.5 |
| | FBC P. THE DESIGNER HAS THE OPTION OF USING POINT OF |
| | USE MIXING VALVES OR SUPPLY COLD WATER ONLY. |
| | |
| | 2) 3.0P: 3RD REQUEST TO SHOW THE HOT WATER RETURN LINE |
| | CONNECTING TO THE MIXING VALVE AND TO THE COLD WATER |
| | INLET PIPE TO THE WATER HEATER- SECTION 607.2.2. FBC P. |
| | |
| | 3) 3.1P: 2ND REQUEST TO CORRECT THE SANITARY RISER |
| | DRAWING SHOWING THE EXISTING 4-INCH SANITARY DRAIN |
| | CONNECTING TO THE NEW GREASE WASTE LINE- SECTION |
| | 107.2.1 WPB AND 1003.3.1 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |