Plan Review Notes
Plan Review Notes For Permit 21050671
Permit Number 21050671
Review Stop P
Sequence Number 3
Notes
Date Text
2021-10-19 11:23:153RD REVIEW FBC-2020 PLUMBING
 PERMIT- 21050671
 6/29/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS 3.0P & 3.1P: 3RD REQUEST- A MASTER
 THERMOSTATIC MIXING VALVE IS SPECIFIED TO PROVIDE
 TEMPERED WATER AT 108 DEGREES F TO ALL FIXTURES EXCEPT
 THE MOP SINK AND 3-COMPARTMENT, HOWEVER THE PLAN AND
 WATER RISER EACH SHOW HOT WATER LINES AT 140 AND 110
 DEGREES F BEING. PLEASE SEE SECTION 202 FOR DEFINITIONS
 OF HOT AND TEMPERED WATER AND CORRECT THE PLAN. PLEASE
 NOTE THAT THE TEMPERED WATER IS ONLY REQUIRED FOR THE
 LAVATORIES REQUIRED FOR THE LAVATORIES- SECTION 419.5
 FBC P. THE DESIGNER HAS THE OPTION OF USING POINT OF
 USE MIXING VALVES OR SUPPLY COLD WATER ONLY.
  
 2) 3.0P: 3RD REQUEST TO SHOW THE HOT WATER RETURN LINE
 CONNECTING TO THE MIXING VALVE AND TO THE COLD WATER
 INLET PIPE TO THE WATER HEATER- SECTION 607.2.2. FBC P.
  
 3) 3.1P: 2ND REQUEST TO CORRECT THE SANITARY RISER
 DRAWING SHOWING THE EXISTING 4-INCH SANITARY DRAIN
 CONNECTING TO THE NEW GREASE WASTE LINE- SECTION
 107.2.1 WPB AND 1003.3.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  