Plan Review Notes
Plan Review Notes For Permit 21050671
Permit Number 21050671
Review Stop G
Sequence Number 3
Notes
Date Text
2021-10-19 11:21:373RD REVIEW FBC-2020 FUEL GAS
 PERMIT- 21050671
 10/19/21
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 3.1P: REFER TO PREVIOUSLY FAILED COMMENT #2
 FROM THE 1ST AND 2ND REVIEW PRINTED BELOW. PLEASE NOTE
 THAT THE LETTER FROM THE PRIMO ROASTING CEO DOES NOT
 PROVIDE INFORMATION OR EVIDENCE OF ANZI STANDARD
 APPROVAL FOR THE GAS BURNER AND ASSOCIATED COMPONENTS-
 SECTION 623.1 FBC FG.
 FAILED. 3.0P & 3.1P: SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE NEW COFFEE ROASTER- SECTION
 305.1 FBC FG. PLEASE HIGHLIGHT OR MARKUP THE SPEC TO
 SHOW THE LISTING STANDARD, BTU LOAD, AND GAS INPUT
 PRESSURE. THE SUBMITTED ROASTER SPECS DO NOT SHOW THE
 LISTING STANDARD, GAS INPUT PRESSURE, OR CATEGORY OF
 THE CATEGORY OF THE APPLIANCE. PLEASE REFER TO SECTIONS
 305.1 AND 623.1 FBC FG FOR LISTING REQUIREMENTS, AND
 SECTION 410.2- INPUT PRESSURE IS REQUIRED FOR
 DETERMINING THE REQUIRED SUPPLY PIPE PRESSURE AND
 REGULATOR SELECTION. ALSO MISSING WITH THE SUBMITTAL
 ARE MANUFACTURER?S INSTALLATION GUIDELINES FOR
 SUPPLYING COMBUSTION AIR, MAKEUP AIR, AND PROPER
 VENTING OF THE EQUIPMENT. THE CATEGORY OF THE APPLIANCE
 NEEDS TO BE ESTABLISHED IN ORDER FOR A COMPLETE REVIEW
 OF THE EXHAUST/VENT SYSTEM. PLEASE INDICATE CATEGORY I,
 II, III, OR IV PER SECTIONS 202, 503.6.9.1, & &
 503.6.9.3. FBC FG.
  
 2) SHEET 3.1P: REFER TO PREVIOUSLY FAILED COMMENT 3
 FROM THE 1ST AND 2ND REVIEWS PRINTED BELOW. THE REVISED
 PLAN SHOWS THE COMBUSTION AIR OPENING IN THE WRONG
 LOCATION. THE OPENING SHALL COMMENCE WITHIN 12 INCHES
 OF THE TOP OF THE ENCLOSURE- SECTION 304.6.2 FBC FG.
 FAILED. 3.0P & 3.1P: PROVIDE COMBUSTION AIR
 CALCULATIONS FOR THE COFFEE ROASTER AND INDICATE HOW
 THE AIR IS BEING SUPPLIED- SECTION 304.1 FBC FG. THE
 RESPONSE NARRATIVE INDICATES INDOOR COMBUSTION AIR IS
 TO BE USED, HOWEVER THE PLAN SHOWS A CALCULATION FOR
 MECHANICALLY SUPPLIED AIR PER 304.9 USING AN OPENING TO
 THE OUTDOORS: A) MECHANICAL AIR MUST BE SUPPLIED BY AN
 AIR SUPPLY SYSTEM- MEANING CONDUCTED FROM A SUPPLY
 UNIT. COMBUSTION AIR THROUGH ONE WALL OPENING SHALL
 COMPLY WITH 304.6.2- 1 SQ. INCH PER 3000 BTUH. SEE
 COMMENT #3 FOR COMBUSTION AIR/VENTING COMPLIANCES.
  
 3) SHEETS 4.0M & 4.1M: REFER TO PREVIOUS REVIEW COMMENT
 #4 PRINTED BELOW.
 FAILED. 3.0P & 3.1P: THE TYPE AND SIZE OF
 EXHAUST/VENTING SYSTEM IS DEPENDENT ON THE CATEGORY OF
 THE APPLIANCE. PLEASE INDICATE CATEGORY I, II, III, OR
 IV PER SECTIONS 202, 503.6.9.1 & 503.6.9.3.FBC FG.
 A) CLARIFY HOW THE SYSTEM WAS DESIGNED- SUBMIT COFFEE
 ROASTERS VENTING/MAKEUP-COMBUSTION AIR SYSTEM
 SPECIFICATIONS AND GUIDELINES- 305.1, 503.3, 503.3.1 &
 623.1.
 B) PROVIDE EXHAUST/VENT DUCTS SIZING CALCULATIONS AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 GUIDELINES FOR THE VENT SYSTEM.
 C) PROVIDE A DIMENSIONED EXHAUST/VENT DIAGRAM SHOWING
 CONNECTOR AND TOTAL RUN LENGTH OF THE SYSTEM CONSISTENT
 WITH THE MANUFACTURER'S SPECIFICATIONS AND/OR
 ENGINEERED CALCULATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  