| 2021-08-26 15:14:48 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21050671 |
| | 6/29/21 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW |
| | WITH ADDITIONAL NOTED IN CAP LETTERS. |
| | |
| | 10) FAILED. 3.1P: ONE HAND SINK LABEL IS MISSING IN THE |
| | WATER RISER- SECTION 107.2.1 WPB. PROVIDE THE MISSING |
| | HS LABEL. |
| | |
| | 11) FAILED. 3.1P WATER RISER: PLEASE PROVIDE A |
| | DIFFERENT LINE SYMBOL FOR THE HOT WATER RETURN LINE. |
| | THE SAME HOT WATER SYMBOL IS BEING USED TO DESIGNATE HW |
| | AT 110 DEGREES, HW AT 140 DEGREES, AND HW RETURN. REFER |
| | TO THE MASTER MIXING VALVE DETAIL ON SHEET 3.0P: THE |
| | DETAIL SHOWS INLETS FOR 140 DEGREE HW AND CW, AND ONE |
| | OUTLET FOR 110 DEGREE TEMPERED. NEITHER THE WATER RISER |
| | NOR THE ENLARGED WATER HEATER PIPING DETAIL MATCH WITH |
| | THE VALVE DETAIL. PLEASE REFER TO SECTION 607.2.2 FBC P |
| | AND REVISE THE DRAWINGS- WHERE A THERMOSTATIC MIXING |
| | VALVE IS USED IN A SYSTEM WITH A HOT WATER |
| | RECIRCULATING PUMP, THE HOT WATER OR TEMPERED WATER |
| | RETURN LINE SHALL BE ROUTED TO THE COLD WATER INLET |
| | PIPE OF THE WATER HEATER AND THE COLD WATER INLET PIPE |
| | OR THE HOT WATER RETURN CONNECTION OF THE THERMOSTATIC |
| | MIXING VALVE. A) PLRASE LABEL THE MIXING VALVE ON THE |
| | RISER DRAING. THE REQUESTED LINE SYMBOL CHANGEES WERE |
| | NOT PROVIDED. |
| | |
| | 14) FAILED. 3.1P: PROVIDE A PLUMBING FIXTURE SCHEDULE |
| | LISTING MAKES AND MODELS BATHROOM FIXTURES, MOP SINK, |
| | 3-COMPARTMENT SINK, HAND SINKS, DUMP SINK, FLOOR SINKS, |
| | FLOOR DRAIN, AND WATER FILTER SYSTEM- SECTIONS |
| | 107.3.5.1.3 & 107.2.1 WPB. THE MOP SINK, 3-COMPARTMENT |
| | SINK, HAND SINKS, DUMP SINK, FLOOR SINKS, FLOOR DRAIN, |
| | AND WATER FILTER SYSTEM WERE NOT INCLUDED IN THE |
| | FIXTURE SCHEDULE HOWEVER THESE ITEMS MAY BE DEFERRED IF |
| | NECESSARY. PLEASE PROVIDE A LIST OF ALL REQUESTED |
| | DEFERRED SUBMITTALS ON THE PLAN- SECTION 107.3.4.1 WPB. |
| | |
| | 15) FAILED. 3.1P: PROVIDE A DEVICE SCHEDULE LISTING |
| | MAKES AND MODELS OF WATER HAMMER ARRESTORS, MIXING |
| | VALVES, RECIRCULATION PUMP, AND BACKFLOW PREVENTERS- |
| | SECTIONS 107.3.5.1.3 & 107.2.1 WPB. A DEVICE SCHEDULE |
| | WAS NOT PROVIDED HOWEVER THE WATER HAMMER ARRESTORS, |
| | MIXING VALVES, AND BACKFLOW PREVENTERS MAY BE DEFERRED |
| | SUBMITTALS IF NECESSARY. PLEASE PROVIDE A LIST OF ALL |
| | REQUESTED DEFERRED SUBMITTALS ON THE PLAN- SECTION |
| | 107.3.4.1 WPB. |
| | |
| | 17) FAILED. 3.1P GREASE INTERCEPTOR: PLEASE NOTE A |
| | SEPARATE PERMIT IS REQUIRED FOR INSTALLATION OF THE |
| | INTERCEPTOR AND A COMPLETE PLANS AND SPECIFICATIONS |
| | SHALL BE SUBMITTED INCLUDING A CIVIL PLAN- SECTION |
| | 107.2.1 WPB. FOR THE PURPOSES OF THIS PERMIT PLEASE |
| | SHOW REQUIRED CLEANOUTS AT THE INLET AND OUTLET OF THE |
| | INTERCEPTOR AND THE LOCATION OF THE SAMPLING PORT. |
| | PROVIDE A DETAIL FOR INSTALLATION OF THE PORT PER |
| | MANUFACTURER?S SPECIFICATIONS- SECTION 1003.3.3 FBC P. |
| | THE GREASE INTERCEPTOR IS INDICATED TO BE A SCHIER GB50 |
| | ON SHEET 3.0P, AND A GBHF-250-250 ON SHEET 3.1P. |
| | |
| | A) FAILED. 3.1P: PROVIDE SIZING CALCULATIONS FOR THE |
| | INTERCEPTOR IN ACCORDANCE WITH ASME A112.14.3, ASME |
| | A112.14.4, ASME A112.14.6, CSA B481.3 OR PDI G101- |
| | SECTION 1003.3.3 FBC P. THE CALCULATIONS ON SHEET 3,0P |
| | DO NOT INCLUDE THE DUMP SINK. |
| | |
| | NEW COMMENTS. |
| | |
| | 1) 3.0P & 3.1P: THE 4-INCH EXISTING SANITARY IS SHOWN |
| | CONNECTING TO THE GREASE WASTE LINE IN THE SANITARY |
| | RISER DRAWING- SECTION 107.2.1 WPB. |
| | |
| | 2) 3.0: THE LOCATION OF THE CLEANOUT AT THE JUNCTION OF |
| | THE SANITARY AND SEWER DRAIN NOT PROVIDED. |
| | |
| | 3) 3.0P & 3.1P: CORRECT THE SUPPLY PIPING LAYOUT TO THE |
| | URINAL AND LAVATORY ON 3.0P- 107.2.1 WPB. |
| | |
| | 4) 3.0P & 3.1P: THE PLAN IS NOT SHOWING HOW TEMPERED |
| | WATER WILL BE PROVIDED TO THE LAVATORIES AS REQUIRED BY |
| | SECTION 419.5 FBC P. PLEASE NOTE THE MASTER MIXING |
| | VALVE IS SUPPLYING HOT WATER AT 110 DEGREES F. TEMPERED |
| | WATER IS DEFINED AS WATER HAVING A TEMPERATURE RANGE |
| | BETWEEN 85 DEGREES AND 110 DEGREES F. |
| | |
| | 5) 1.1A, 3.0P & 3.1P: THE WATER FILTERING SYSTEM IS NOT |
| | INCLUDED IN THE EQUIPMENT SCHEDULE, AND THE WATER RISER |
| | IS NOT SHOWING ALL THE FILTERED WATER SUPPLY LINES TO |
| | THE EQUIPMENT IN THE SCHEDULE. PLEASE MODIFY THE RISER |
| | OR PROVIDE A SEPARATE FILTERED WATER SYSTEM RISER- |
| | SECTION 107.2.1. PLEASE NOTE THAT INDIVIDUAL BACKFLOW |
| | PREVENTERS ARE REQUIRED ON EACH SUPPLY LINE TO THE |
| | COFFEE EQUIPMENT. |
| | |
| | 6) 3.0P & 3.1P: IT IS ACKNOWLEDGED THAT THE GREASE |
| | INTERCEPTOR WILL BE UNDER SEPARATE PERMIT, HOWEVER MORE |
| | INFORMATION UNDER THE MAIN PERMIT IS REQUIRED INCLUDING |
| | THE JUNCTION LOCATIONS OF THE EXISTING SANITARY, GREASE |
| | WASTE OUTLET PIPE, AND EXISTING SEWER LINE. PLEASE ALSO |
| | SHOW THE LOCATION OF THE INTERCEPTOR SAMPLING PORT AND |
| | CLARIFY IF THE INTERCEPTOR IS LOCATED IN A DRIVE OR |
| | LANDSCAPED AREA. PLEASE NOTE THAT HEAVY DUTY TRAFFIC |
| | LIDS AT ACCESS COVERS ARE REQUIRED FOR INTERCEPTORS IN |
| | DRIVE AREAS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |