2021-08-26 15:14:481ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21050671
 6/29/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
 FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW
 WITH ADDITIONAL NOTED IN CAP LETTERS.
  
 10) FAILED. 3.1P: ONE HAND SINK LABEL IS MISSING IN THE
 WATER RISER- SECTION 107.2.1 WPB. PROVIDE THE MISSING
 HS LABEL.
  
 11) FAILED. 3.1P WATER RISER: PLEASE PROVIDE A
 DIFFERENT LINE SYMBOL FOR THE HOT WATER RETURN LINE.
 THE SAME HOT WATER SYMBOL IS BEING USED TO DESIGNATE HW
 AT 110 DEGREES, HW AT 140 DEGREES, AND HW RETURN. REFER
 TO THE MASTER MIXING VALVE DETAIL ON SHEET 3.0P: THE
 DETAIL SHOWS INLETS FOR 140 DEGREE HW AND CW, AND ONE
 OUTLET FOR 110 DEGREE TEMPERED. NEITHER THE WATER RISER
 NOR THE ENLARGED WATER HEATER PIPING DETAIL MATCH WITH
 THE VALVE DETAIL. PLEASE REFER TO SECTION 607.2.2 FBC P
 AND REVISE THE DRAWINGS- WHERE A THERMOSTATIC MIXING
 VALVE IS USED IN A SYSTEM WITH A HOT WATER
 RECIRCULATING PUMP, THE HOT WATER OR TEMPERED WATER
 RETURN LINE SHALL BE ROUTED TO THE COLD WATER INLET
 PIPE OF THE WATER HEATER AND THE COLD WATER INLET PIPE
 OR THE HOT WATER RETURN CONNECTION OF THE THERMOSTATIC
 MIXING VALVE. A) PLRASE LABEL THE MIXING VALVE ON THE
 RISER DRAING. THE REQUESTED LINE SYMBOL CHANGEES WERE
 NOT PROVIDED.
  
 14) FAILED. 3.1P: PROVIDE A PLUMBING FIXTURE SCHEDULE
 LISTING MAKES AND MODELS BATHROOM FIXTURES, MOP SINK,
 3-COMPARTMENT SINK, HAND SINKS, DUMP SINK, FLOOR SINKS,
 FLOOR DRAIN, AND WATER FILTER SYSTEM- SECTIONS
 107.3.5.1.3 & 107.2.1 WPB. THE MOP SINK, 3-COMPARTMENT
 SINK, HAND SINKS, DUMP SINK, FLOOR SINKS, FLOOR DRAIN,
 AND WATER FILTER SYSTEM WERE NOT INCLUDED IN THE
 FIXTURE SCHEDULE HOWEVER THESE ITEMS MAY BE DEFERRED IF
 NECESSARY. PLEASE PROVIDE A LIST OF ALL REQUESTED
 DEFERRED SUBMITTALS ON THE PLAN- SECTION 107.3.4.1 WPB.
  
 15) FAILED. 3.1P: PROVIDE A DEVICE SCHEDULE LISTING
 MAKES AND MODELS OF WATER HAMMER ARRESTORS, MIXING
 VALVES, RECIRCULATION PUMP, AND BACKFLOW PREVENTERS-
 SECTIONS 107.3.5.1.3 & 107.2.1 WPB. A DEVICE SCHEDULE
 WAS NOT PROVIDED HOWEVER THE WATER HAMMER ARRESTORS,
 MIXING VALVES, AND BACKFLOW PREVENTERS MAY BE DEFERRED
 SUBMITTALS IF NECESSARY. PLEASE PROVIDE A LIST OF ALL
 REQUESTED DEFERRED SUBMITTALS ON THE PLAN- SECTION
 107.3.4.1 WPB.
  
 17) FAILED. 3.1P GREASE INTERCEPTOR: PLEASE NOTE A
 SEPARATE PERMIT IS REQUIRED FOR INSTALLATION OF THE
 INTERCEPTOR AND A COMPLETE PLANS AND SPECIFICATIONS
 SHALL BE SUBMITTED INCLUDING A CIVIL PLAN- SECTION
 107.2.1 WPB. FOR THE PURPOSES OF THIS PERMIT PLEASE
 SHOW REQUIRED CLEANOUTS AT THE INLET AND OUTLET OF THE
 INTERCEPTOR AND THE LOCATION OF THE SAMPLING PORT.
 PROVIDE A DETAIL FOR INSTALLATION OF THE PORT PER
 MANUFACTURER?S SPECIFICATIONS- SECTION 1003.3.3 FBC P.
 THE GREASE INTERCEPTOR IS INDICATED TO BE A SCHIER GB50
 ON SHEET 3.0P, AND A GBHF-250-250 ON SHEET 3.1P.
  
 A) FAILED. 3.1P: PROVIDE SIZING CALCULATIONS FOR THE
 INTERCEPTOR IN ACCORDANCE WITH ASME A112.14.3, ASME
 A112.14.4, ASME A112.14.6, CSA B481.3 OR PDI G101-
 SECTION 1003.3.3 FBC P. THE CALCULATIONS ON SHEET 3,0P
 DO NOT INCLUDE THE DUMP SINK.
  
 NEW COMMENTS.
  
 1) 3.0P & 3.1P: THE 4-INCH EXISTING SANITARY IS SHOWN
 CONNECTING TO THE GREASE WASTE LINE IN THE SANITARY
 RISER DRAWING- SECTION 107.2.1 WPB.
  
 2) 3.0: THE LOCATION OF THE CLEANOUT AT THE JUNCTION OF
 THE SANITARY AND SEWER DRAIN NOT PROVIDED.
  
 3) 3.0P & 3.1P: CORRECT THE SUPPLY PIPING LAYOUT TO THE
 URINAL AND LAVATORY ON 3.0P- 107.2.1 WPB.
  
 4) 3.0P & 3.1P: THE PLAN IS NOT SHOWING HOW TEMPERED
 WATER WILL BE PROVIDED TO THE LAVATORIES AS REQUIRED BY
 SECTION 419.5 FBC P. PLEASE NOTE THE MASTER MIXING
 VALVE IS SUPPLYING HOT WATER AT 110 DEGREES F. TEMPERED
 WATER IS DEFINED AS WATER HAVING A TEMPERATURE RANGE
 BETWEEN 85 DEGREES AND 110 DEGREES F.
  
 5) 1.1A, 3.0P & 3.1P: THE WATER FILTERING SYSTEM IS NOT
 INCLUDED IN THE EQUIPMENT SCHEDULE, AND THE WATER RISER
 IS NOT SHOWING ALL THE FILTERED WATER SUPPLY LINES TO
 THE EQUIPMENT IN THE SCHEDULE. PLEASE MODIFY THE RISER
 OR PROVIDE A SEPARATE FILTERED WATER SYSTEM RISER-
 SECTION 107.2.1. PLEASE NOTE THAT INDIVIDUAL BACKFLOW
 PREVENTERS ARE REQUIRED ON EACH SUPPLY LINE TO THE
 COFFEE EQUIPMENT.
  
 6) 3.0P & 3.1P: IT IS ACKNOWLEDGED THAT THE GREASE
 INTERCEPTOR WILL BE UNDER SEPARATE PERMIT, HOWEVER MORE
 INFORMATION UNDER THE MAIN PERMIT IS REQUIRED INCLUDING
 THE JUNCTION LOCATIONS OF THE EXISTING SANITARY, GREASE
 WASTE OUTLET PIPE, AND EXISTING SEWER LINE. PLEASE ALSO
 SHOW THE LOCATION OF THE INTERCEPTOR SAMPLING PORT AND
 CLARIFY IF THE INTERCEPTOR IS LOCATED IN A DRIVE OR
 LANDSCAPED AREA. PLEASE NOTE THAT HEAVY DUTY TRAFFIC
 LIDS AT ACCESS COVERS ARE REQUIRED FOR INTERCEPTORS IN
 DRIVE AREAS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  