| 2021-08-25 12:47:58 | 2ND REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21050671 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE ATTACHED SPECIFICATIONS DO NOT SHOW THE EXHAUST |
| | PIPING DETAILS. PLEASE PROVIDE DETAILS FOR THE EXHAUST |
| | SYSTEM OF THIS ROASTER, TYPE OF PIPE, SIZE OF PIPE, |
| | LENGTH OF PIPE. INFORMATION FROM THE MANUFACTURER |
| | REFERENCING THE EXHAUST PIPING USED. FBC 107.2.1 |
| | |
| | 2) SHEET 4.1M: PLEASE PROVIDE THE USE OF SPACE BASED ON |
| | FBC M TABLE 403.3.1.1 FOR THE OUTDOOR AIR CALCULATIONS. |
| | ARE YOU USING KITCHEN FOR THE PREP AREA AND DINING FOR |
| | THE CUSTOMER AREA? ACCORDING TO FBC M 403.3.1.1 WE MUST |
| | US THE TABLE FOR CALCULATING THE NUMBER OF PEOPLE IN |
| | EACH SPACE NOT THE ARCHITECT?S OCCUPANT LOAD. PLEASE |
| | KEEP IN MIND FOOTNOTE (A) ALLOWS US TO USE THE NET AREA |
| | AND NOT THE GROSS FLOOR AREA. |
| | |
| | 3) PLEASE SHOW HOW YOU WILL BE BRINGING IN THE MAKEUP |
| | AIR FOR THE EXHAUST FAN ON THE ROASTER ( 1125 CFM?S). |
| | FBC FG 304.9.1 |
| | |
| | 4) THE ROASTER VENTILATION DETAIL SUBMITTED ON SHEET |
| | 4.1M DOES NOT DEPICT THE BUILDING WHERE THIS TENANT |
| | SPACE IS LOCATED. THIS IS A 3 STORY WITH RETAIL ON THE |
| | FIRST FLOOR BUT RESIDENTIAL ON THE 2ND AND 3RD FLOORS. |
| | THIS DRAWING SHOWS ?ZERO CLEARANCE PIPE THRU WALL BOXED |
| | OUT TO ROOF? BUT DOES NOT SHOW BOTH FLOORS ABOVE NOR |
| | DOES IT HAVE A NOTE DESCRIBING THIS SITUATION. THIS |
| | DRAWING ALSO SHOWS A FD IN THE ROASTER EXHAUST PIPE |
| | ABOVE THE FLOOR IN WHAT APPEARS TO BE A BOX. PLEASE |
| | SHOW THE MANUFACTURER?S INSTALLATION INSTRUCTIONS FOR |
| | THIS TYPE OF PIPING METHOD. |
| | |
| | 5) SHEET 4.1M: THE ROASTER VENTILATION DETAIL DOES NOT |
| | SHOW THE EXHAUST FOR THE COOLING TUB. |
| | |
| | |
| | 6) PLEASE PROVIDE THE LISTING FOR THIS APPLIANCE. FBC M |
| | 301.7 |
| | |
| | 7) PLEASE EXPLAIN YOUR ANSWER TO MY 1ST CYCLE COMMENT |
| | NUMBER (5): PLEASE SHOW THE OUTDOOR AIR DUCT FOR BOTH |
| | AHU-1 UNITS. YOUR ANSWER WAS ?BOTH AIR HANDLERS UNITS |
| | HAVE OUTSIDE AIR DUCT WORK TO THE KNOCK OUT PROVIDED |
| | WITH BUILDING? PLEASE SHOW THE OUTDOOR AIR DUCT WORK |
| | AND SIZE ON THE DRAWING. FBC 107.2.1 |
| | |
| | 8) 1ST CYCLE REVIEW COMMENT NUMBER (6) AHU-2 FOR THE |
| | KITCHEN AREA: CFM?S ON SHEET 4.0M SHOWS A TOTAL OF 2200 |
| | CFM?S OF SUPPLY AIR BEING SUPPLIED INTO THE KITCHEN |
| | AREA. SHEET 4.1M INDICATES THE MAX. CFM OF SUPPLY FOR |
| | THIS UNIT IS 2000 CFM?S. PLEASE BE CONSISTENT. FBC |
| | 107.2.1 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |