Plan Review Notes
Plan Review Notes For Permit 21050671
Permit Number 21050671
Review Stop G
Sequence Number 2
Notes
Date Text
2021-08-26 15:08:202ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21050671
 8/26/21
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
  
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW LISTED BELOW WITH ADDITIONAL NOTES IN CAPS.
  
 2) FAILED. 3.0P & 3.1P: SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE NEW COFFEE ROASTER- SECTION
 305.1 FBC FG. PLEASE HIGHLIGHT OR MARKUP THE SPEC TO
 SHOW THE LISTING STANDARD, BTU LOAD, AND GAS INPUT
 PRESSURE. THE SUBMITTED ROASTER SPECS DO NOT SHOW THE
 LISTING STANDARD, GAS INPUT PRESSURE, OR CATEGORY OF
 THE CATEGORY OF THE APPLIANCE. PLEASE REFER TO SECTIONS
 305.1 AND 623.1 FBC FG FOR LISTING REQUIREMENTS, AND
 SECTION 410.2- INPUT PRESSURE IS REQUIRED FOR
 DETERMINING THE REQUIRED SUPPLY PIPE PRESSURE AND
 REGULATOR SELECTION. ALSO MISSING WITH THE SUBMITTAL
 ARE MANUFACTURER?S INSTALLATION GUIDELINES FOR
 SUPPLYING COMBUSTION AIR, MAKEUP AIR, AND PROPER
 VENTING OF THE EQUIPMENT. PLEASE NOTE THE ROASTER SPECS
 INDICATE A BTUH LOAD OF 144,000 NOT 140,000 AS
 INDICATED ON THE RISER. THE CATEGORY OF THE APPLIANCE
 NEEDS TO BE ESTABLISHED IN ORDER FOR A COMPLETE REVIEW
 OF THE EXHAUST/VENT SYSTEM. PLEASE INDICATE CATEGORY I,
 II, III, OR IV PER SECTIONS 202, 503.6.9.1, & &
 503.6.9.3. FBC FG.
  
 3) FAILED. 3.0P & 3.1P: PROVIDE COMBUSTION AIR
 CALCULATIONS FOR THE COFFEE ROASTER AND INDICATE HOW
 THE AIR IS BEING SUPPLIED- SECTION 304.1 FBC FG. THE
 RESPONSE NARRATIVE INDICATES INDOOR COMBUSTION AIR IS
 TO BE USED, HOWEVER THE PLAN SHOWS A CALCULATION FOR
 MECHANICALLY SUPPLIED AIR PER 304.9 USING AN OPENING TO
 THE OUTDOORS: A) MECHANICAL AIR MUST BE SUPPLIED BY AN
 AIR SUPPLY SYSTEM- MEANING CONDUCTED FROM A SUPPLY
 UNIT. COMBUSTION AIR THROUGH ONE WALL OPENING SHALL
 COMPLY WITH 304.6.2- 1 SQ. INCH PER 3000 BTUH. SEE
 COMMENT #3 FOR COMBUSTION AIR/VENTING COMPLIANCES.
  
 4) FAILED. 3.0P & 3.1P: PROVIDE GAS VENTING PLANS FOR
 THE ROASTER- SECTIONS 305.1, 502.1, 502.5, AND 503.1-.
 THE DRAWING SPEARS TO INDICATE TWO VENT DUCTS FOR THE
 ROASTER THAT ARE PENETRATING THROUGH THE WALL AND
 TURNING UPWARD. PLEASE PROVIDE A DIAGRAM AND ELEVATION
 VIEW SHOWING THE TYPES AND SIZES OF VENT FLUES OR
 DUCTS, HORIZONTAL CONNECTORS, VERTICAL FLUES, AND
 TERMINATION CAPS. PLEASE PROVIDE THE VENT TERMINATION
 CLEARANCE DISTANCES TO DOOR AND WINDOW OPENINGS INTO
 THE BUILDING- SECTIONS 305.1, 403.4, 503.6 & 503.8 FBC
 FG. RTHE TYPE AND SIZE OF EXHAUST/VENTING SYSTEM IS
 DEPENDENT ON THE CATEGORY OF THE APPLIANCE. PLEASE
 INDICATE CATEGORY I, II, III, OR IV PER SECTIONS 202,
 503.6.9.1 & 503.6.9.3.FBC FG. THE CURRENT
 EXHAUST/VENTING PLAN ON SHEET 4.1M IS INCOMPLETE AND
 SHOWS ONLY ONE THE TWO DUCT SYSTEMS.
 A) CLARIFY HOW THE SYSTEM WAS DESIGNED- SUBMIT COFFEE
 ROASTERS VENTING/MAKEUP-COMBUSTION AIR SYSTEM
 SPECIFICATIONS AND GUIDELINES- 305.1, 503.3, 503.3.1 &
 623.1.
  
 B) PROVIDE EXHAUST/VENT DUCTS SIZING CALCULATIONS AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 GUIDELINES FOR THE SINGLE-WALL ZERO CLEARANCE DUCT-
 305.1, 503.3, 503.3.1.503.7.9.
  
 C) PROVIDE A DIMENSIONED EXHAUST/VENT DIAGRAM SHOWING
 CONNECTOR AND TOTAL RUN LENGTH OF THE SYSTEM CONSISTENT
 WITH THE MANUFACTURER'S SPECIFICATIONS AND/OR
 ENGINEERED CALCULATIONS.
  
 D) PLEASE NOTE THE FOLLOWING LIMITATIONS OF USE FOR
 SINGLE WALL DUCT-
  
 SECTION 503.7.3: SINGLE WALL PIPE SHALL EXTEND NOT LESS
 THAN 2 FT. HIGHER THAN ANY PORTION OF A BUILDING WITHIN
 A HORIZONTAL DISTANCE OF 10 FT. THE DRAWNIG IS
 NON-COMPLIANT.
  
 503.7.4: SINGLE-WALL METAL DUCT SHALL BE USED ONLY FOR
 RUNS DIRECTLY FROM THE SPACE IN WHICH THE APPLIANCE IS
 LOCATED THROUGH THE ROOF OR EXTERIOR WALL TO THE
 OUTDOOR ATMOSPHERE. DRAWING IS NON-COMPLIANT.
  
 503.7.5: A PIPE PASSING THROUGH A ROOF SHALL EXTEND
 WITHOUT INTERRUPTION THROUGH THE ROOF FLASHING, ROOF
 JACK OR ROOF THIMBLE. WHERE A SINGLE-WALL METAL PIPE
 PASSES THROUGH A ROOF CONSTRUCTED OF COMBUSTIBLE
 MATERIAL, A NONCOMBUSTIBLE, NONVENTILATING THIMBLE
 SHALL BE USED AT THE POINT OF PASSAGE. THE THIMBLE
 SHALL EXTEND NOT LESS THAN 18 INCHES (457 MM) ABOVE AND
 6 INCHES (152 MM) BELOW THE ROOF WITH THE ANNULAR SPACE
 OPEN AT THE BOTTOM AND CLOSED ONLY AT THE TOP. THE
 THIMBLE SHALL BE SIZED IN ACCORDANCE WITH SECTION
 503.7.7. DRAWING IS NON-COMPLIANT.
  
 503.7.6: SINGLE-WALL METAL PIPE SHALL NOT ORIGINATE IN
 ANY UNOCCUPIED ATTIC OR CONCEALED SPACE AND SHALL NOT
 PASS THROUGH ANY ATTIC, INSIDE WALL, CONCEALED SPACE OR
 FLOOR. THE INSTALLATION OF A SINGLE-WALL METAL PIPE
 THROUGH AN EXTERIOR COMBUSTIBLE WALL SHALL COMPLY WITH
 SECTION 503.7.7. DRAWING IS NON-COMPLIANT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  