Plan Review Notes
Plan Review Notes For Permit 21050671
Permit Number 21050671
Review Stop B
Sequence Number 2
Notes
Date Text
2021-08-24 16:10:15****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND BUILDING REVIEW DENIED:
  
 1)FBC B 107.2.1, DISCREPANCY IN PLAN SHEETS C-1 & 1.3A
 STILL EXIST. PLEASE CORRECT THE OCCUPANCY NUMBERS
 TO MATCH. SHEET C-1 INDICATES 78 TOTAL NUMBER OF SEATS
 AND SHEET 1.3A INDICATES 72 MINIMUM OCCUPANT
 LOAD.
 2A) OK
 2B) OK
 2C) OK
 2D) OK
 3) OK
 4) OK
 5) OK
 6) FAILED, FBC B 1010.1.2.1, (PLAN SHEETS 1.0A & 1.3A)
 THE DOOR STILL SHOWS SWINGING INWARD. THIS DOOR
 MUST SWING OUTWARD AS IT IS AN EGRESS DOOR (PART OF A
 MEANS OF EGRESS).
 7) FAILED, FBC B 1028.4.2, MORE INFORMATION IS REQUIRED
 TO SHOW THE FIRE RATING HAS BEEN MET FOR THE WALL
 AND WALL OPENINGS. ALSO, THE NEW CHASE DETAIL FOR THE
 MECHANICAL (ROASTER) EXHAUST UNDER THE SOFFIT DOES
 NOT APPEAR TO FIT THE SIDE OF THE BUILDING. THIS
 BUILDING APPEARS TO BE THREE STORIES AT THIS LOCATION.
 PLEASE
 VERIFY.
 8) OK
 9) OK