Notes
Date Text
2021-06-29 12:00:271ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21050671
 6/29/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET C1: THE PLUMBING FIXTURE CALCULATIONS BASED ON
 72 OCCUPANTS DOES NOT MATCH THE 129 NUMBER OF SEATS
 SHOWN. PLEASE CORRECT- TABLE 403.1 FBC P.
  
 2) 1.0A & 1.4A: PLEASE PROVIDE ENLARGED MEN'S AND
 WOMEN'S TOILET ROOM ENLARGED DIMENSIONED DRAWINGS ON
 1.4A THAT MATCH THE FLOOR PLAN DRAWINGS ON 1.0A. THE
 FLOOR PLAN SHOWS DOORS SWINGING IN TO THE TOILET ROOMS
 WHICH IS NOT ALLOWED PER SECTION 603.2.3 FBC ACC. THE
 FLOOR PLAN ALSO DOES NOT PROVIDE A WIDTH MEASUREMENT
 FOR THE WOMEN'S TOILET ROOM- SECTION 107.2.1 WPB.
  
 3) 1.4A: LOCATION OF THE TOILET PAPER DISPENSER IS NOT
 SHOWN TO BE IN COMPLIANCE WITH SECTION 604.7 FBC ACC.
  
 4) 1.4A: PROVIDE AN ELEVATION VIEW OF THE CONDIMENTS
 COUNTER TO VERIFY ACCESSIBILITY COMPLIANCES- SECTIONS-
 904.5 & 308 FBC ACC.
  
 5) 1.1A, 3.0P, & 3.1P: THE HAND SINKS- #10, #28, AND
 THE FLOOR SINK BY THE ICE MAKER AND BIN SHALL NOT DRAIN
 IN TO THE GREASE WASTE LINE AND INTERCEPTOR- SECTION
 1003.3.1 FBC P. THE FIXTURES ARE NOT CONSIDERED TO BE
 SIGNIFICANT GREASE CONTRIBUTORS.
  
 6) 1.1A, 3.0P, & 3.1P: THE DUMP SINK #21 REQUIRES AN
 INDIRECT WASTE- SECTION 802.1 FBC P.
  
 7) 1.1A, 3.0P, & 3.1P: HAND SINK #28 APPEARS TO MISSING
 FROM THE ISOMETRIC DRAWINGS.
  
 8) 3.0P: PROVIDE AN EQUIPMENT SCHEDULE FOR THE WATER
 HEATER MAKE AND MODEL AND EFFICIENCY RATING- SECTION
 502.1 FBC P. SHOW THE PAN DRAIN AND PAN DRAIN LINE RUN
 AND TERMINATION LOCATION- SECTIONS 504.6- 504.7.2 FBC
 P.
  
 9) 3.0P: THE SERVICE ACCESS TO THE WATER HEATER APPEARS
 TO BE BLOCKED BY THE ADJACENT SINKS- SECTION 501.4 FBC
 P.
  
 10) 3.1P: ONE HAND SINK LABEL IS MISSING IN THE WATER
 RISER- SECTION 107.2.1 WPB.
  
 11) 3.1P WATER RISER: PLEASE PROVIDE A DIFFERENT LINE
 SYMBOL FOR THE HOT WATER RETURN LINE. THE SAME HOT
 WATER SYMBOL IS BEING USED TO DESIGNATE HW AT 110
 DEGREES, HW AT 140 DEGREES, AND HW RETURN. IT ALSO
 APPEARS THAT NO COLD WATER IS BEING SUPPLIED TO THE
 LAVATORY SINKS.
  
 12) 3.1P: ONE LAVATORY IS NOT LABELED IN THE SANITARY-
 SECTION 107.2.1 WPB.
  
 13) THE URINAL IS NOT INCLUDED IN THE DEFINITION OF A
 BATHROOM GROUP SO THE FIXTURE DRAIN FROM THE URINAL
 SHALL NOT CONNECT INTO THE HORIZONTAL WET VENT-
 SECTIONS 202 AND 912.1 FBC P. THE FIXTURE MUST BE
 INDIVIDUALLY VENTED AND CONNECTION OF THE DRAIN SHALL
 BE DOWNSTREAM OF THE WET VENT.
 14) 3.1P: PROVIDE A PLUMBING FIXTURE SCHEDULE LISTING
 MAKES AND MODELS BATHROOM FIXTURES, MOP SINK,
 3-COMPARTMENT SINK, HAND SINKS, DUMP SINK, FLOOR SINKS,
 FLOOR DRAIN WATER FILTER SYSTEM- SECTIONS 107.3.5.1.3 &
 107.2.1 WPB.
  
 15) 3.1P: PROVIDE A DEVICE SCHEDULE LISTING MAKES AND
 MODELS OF WATER HAMMER ARRESTORS, MIXING VALVES,
 RECIRCULATION PUMP, AND BACKFLOW PREVENTERS- SECTIONS
 107.3.5.1.3 & 107.2.1 WPB.
  
 16) 3.1P: PROVIDE CLEANOUT AT THE JUNCTION OF THE
 SANITARY BUILDING DRAIN AND SEWER LINE- SECTION 708.1.3
 FBC P.
  
 17) 3.1P GREASE INTERCEPTOR: PLEASE NOTE A SEPARATE
 PERMIT IS REQUIRED FOR INSTALLATION OF THE INTERCEPTOR
 AND A COMPLETE PLANS AND SPECIFICATIONS SHALL BE
 SUBMITTED INCLUDING A CIVIL PLAN- SECTION 107.2.1 WPB.
 FOR THE PURPOSES OF THIS PERMIT PLEASE SHOW REQUIRED
 CLEANOUTS AT THE INLET AND OUTLET OF THE INTERCEPTOR
 AND THE LOCATION OF THE SAMPLING PORT. PROVIDE A DETAIL
 FOR INSTALLATION OF THE PORT PER MANUFACTURER?S
 SPECIFICATIONS- SECTION 1003.3.3 FBC P.
  
 A) 3.1P: PROVIDE SIZING CALCULATIONS FOR THE
 INTERCEPTOR IN ACCORDANCE WITH ASME A112.14.3, ASME
 A112.14.4, ASME A112.14.6, CSA B481.3 OR PDI G101-
 SECTION 1003.3.3 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  