| 2021-06-29 12:00:27 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21050671 |
| | 6/29/21 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET C1: THE PLUMBING FIXTURE CALCULATIONS BASED ON |
| | 72 OCCUPANTS DOES NOT MATCH THE 129 NUMBER OF SEATS |
| | SHOWN. PLEASE CORRECT- TABLE 403.1 FBC P. |
| | |
| | 2) 1.0A & 1.4A: PLEASE PROVIDE ENLARGED MEN'S AND |
| | WOMEN'S TOILET ROOM ENLARGED DIMENSIONED DRAWINGS ON |
| | 1.4A THAT MATCH THE FLOOR PLAN DRAWINGS ON 1.0A. THE |
| | FLOOR PLAN SHOWS DOORS SWINGING IN TO THE TOILET ROOMS |
| | WHICH IS NOT ALLOWED PER SECTION 603.2.3 FBC ACC. THE |
| | FLOOR PLAN ALSO DOES NOT PROVIDE A WIDTH MEASUREMENT |
| | FOR THE WOMEN'S TOILET ROOM- SECTION 107.2.1 WPB. |
| | |
| | 3) 1.4A: LOCATION OF THE TOILET PAPER DISPENSER IS NOT |
| | SHOWN TO BE IN COMPLIANCE WITH SECTION 604.7 FBC ACC. |
| | |
| | 4) 1.4A: PROVIDE AN ELEVATION VIEW OF THE CONDIMENTS |
| | COUNTER TO VERIFY ACCESSIBILITY COMPLIANCES- SECTIONS- |
| | 904.5 & 308 FBC ACC. |
| | |
| | 5) 1.1A, 3.0P, & 3.1P: THE HAND SINKS- #10, #28, AND |
| | THE FLOOR SINK BY THE ICE MAKER AND BIN SHALL NOT DRAIN |
| | IN TO THE GREASE WASTE LINE AND INTERCEPTOR- SECTION |
| | 1003.3.1 FBC P. THE FIXTURES ARE NOT CONSIDERED TO BE |
| | SIGNIFICANT GREASE CONTRIBUTORS. |
| | |
| | 6) 1.1A, 3.0P, & 3.1P: THE DUMP SINK #21 REQUIRES AN |
| | INDIRECT WASTE- SECTION 802.1 FBC P. |
| | |
| | 7) 1.1A, 3.0P, & 3.1P: HAND SINK #28 APPEARS TO MISSING |
| | FROM THE ISOMETRIC DRAWINGS. |
| | |
| | 8) 3.0P: PROVIDE AN EQUIPMENT SCHEDULE FOR THE WATER |
| | HEATER MAKE AND MODEL AND EFFICIENCY RATING- SECTION |
| | 502.1 FBC P. SHOW THE PAN DRAIN AND PAN DRAIN LINE RUN |
| | AND TERMINATION LOCATION- SECTIONS 504.6- 504.7.2 FBC |
| | P. |
| | |
| | 9) 3.0P: THE SERVICE ACCESS TO THE WATER HEATER APPEARS |
| | TO BE BLOCKED BY THE ADJACENT SINKS- SECTION 501.4 FBC |
| | P. |
| | |
| | 10) 3.1P: ONE HAND SINK LABEL IS MISSING IN THE WATER |
| | RISER- SECTION 107.2.1 WPB. |
| | |
| | 11) 3.1P WATER RISER: PLEASE PROVIDE A DIFFERENT LINE |
| | SYMBOL FOR THE HOT WATER RETURN LINE. THE SAME HOT |
| | WATER SYMBOL IS BEING USED TO DESIGNATE HW AT 110 |
| | DEGREES, HW AT 140 DEGREES, AND HW RETURN. IT ALSO |
| | APPEARS THAT NO COLD WATER IS BEING SUPPLIED TO THE |
| | LAVATORY SINKS. |
| | |
| | 12) 3.1P: ONE LAVATORY IS NOT LABELED IN THE SANITARY- |
| | SECTION 107.2.1 WPB. |
| | |
| | 13) THE URINAL IS NOT INCLUDED IN THE DEFINITION OF A |
| | BATHROOM GROUP SO THE FIXTURE DRAIN FROM THE URINAL |
| | SHALL NOT CONNECT INTO THE HORIZONTAL WET VENT- |
| | SECTIONS 202 AND 912.1 FBC P. THE FIXTURE MUST BE |
| | INDIVIDUALLY VENTED AND CONNECTION OF THE DRAIN SHALL |
| | BE DOWNSTREAM OF THE WET VENT. |
| | 14) 3.1P: PROVIDE A PLUMBING FIXTURE SCHEDULE LISTING |
| | MAKES AND MODELS BATHROOM FIXTURES, MOP SINK, |
| | 3-COMPARTMENT SINK, HAND SINKS, DUMP SINK, FLOOR SINKS, |
| | FLOOR DRAIN WATER FILTER SYSTEM- SECTIONS 107.3.5.1.3 & |
| | 107.2.1 WPB. |
| | |
| | 15) 3.1P: PROVIDE A DEVICE SCHEDULE LISTING MAKES AND |
| | MODELS OF WATER HAMMER ARRESTORS, MIXING VALVES, |
| | RECIRCULATION PUMP, AND BACKFLOW PREVENTERS- SECTIONS |
| | 107.3.5.1.3 & 107.2.1 WPB. |
| | |
| | 16) 3.1P: PROVIDE CLEANOUT AT THE JUNCTION OF THE |
| | SANITARY BUILDING DRAIN AND SEWER LINE- SECTION 708.1.3 |
| | FBC P. |
| | |
| | 17) 3.1P GREASE INTERCEPTOR: PLEASE NOTE A SEPARATE |
| | PERMIT IS REQUIRED FOR INSTALLATION OF THE INTERCEPTOR |
| | AND A COMPLETE PLANS AND SPECIFICATIONS SHALL BE |
| | SUBMITTED INCLUDING A CIVIL PLAN- SECTION 107.2.1 WPB. |
| | FOR THE PURPOSES OF THIS PERMIT PLEASE SHOW REQUIRED |
| | CLEANOUTS AT THE INLET AND OUTLET OF THE INTERCEPTOR |
| | AND THE LOCATION OF THE SAMPLING PORT. PROVIDE A DETAIL |
| | FOR INSTALLATION OF THE PORT PER MANUFACTURER?S |
| | SPECIFICATIONS- SECTION 1003.3.3 FBC P. |
| | |
| | A) 3.1P: PROVIDE SIZING CALCULATIONS FOR THE |
| | INTERCEPTOR IN ACCORDANCE WITH ASME A112.14.3, ASME |
| | A112.14.4, ASME A112.14.6, CSA B481.3 OR PDI G101- |
| | SECTION 1003.3.3 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |