| 2021-06-22 14:47:38 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21050671 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE |
| | OF SPACE ACCORDING TO FBC M 403.3.1.1 AND TABLE |
| | 403.3.1.1. |
| | |
| | 2) PLEASE PROVIDE THE SPECIFICATIONS FOR THE ROASTING |
| | EQUIPMENT AND THE VENTING OF THIS EQUIPMENT. FBC |
| | 107.2.1 |
| | |
| | 3) PLEASE SHOW THE CONDENSATE PIPING MATERIAL AND |
| | SIZING ALONG WITH THE TERMINATION LOCATION. THE |
| | CONDENSATE IS REQUIRED TO GO TO STORM OR AN APPROVED |
| | OUTDOOR LOCATION. FBC M 307 |
| | |
| | 4) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS FOR THIS TENANT SPACE. |
| | |
| | 5) PLEASE SHOW THE OUTDOOR AIR DUCT FOR BOTH AHU-1 |
| | UNITS. FBC 107.2.1 |
| | |
| | 6) THE KITCHEN AHU-1 IS SUPPLY 2400 CFM?S OF AIR BUT |
| | THE SPECS SHOW IT CAN ONLY SUPPLY 2000 CFM. PLEASE |
| | CORRECT THIS. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |
| | |