| 2021-06-29 12:44:41 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21050671 |
| | 6/29/21 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 3.1P: PROVIDE A COMPLETE GAS RISER DRAWING |
| | THAT INCLUDES ALL NEW AND EXISTING GAS PIPING AND |
| | APPLIANCES BEING SUPPLIED BY THE METER- SECTION 401.4 |
| | FBC FG. THE DRAWING SHOWS A 2 INCH BRANCH LINE |
| | SUPPLYING 879 MBTUH. REFER TO SECTION 402 AND PROVIDE: |
| | A) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| | B) TYPES AND SIZES OF PIPING. |
| | C) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | D) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | E) LOCATIONS OF REGULATORS, SHUTOFF VALVES, DRIPLEGS, |
| | AND PIPE UNIONS. |
| | F) OUTLET PRESSURES AT REGULATORS. |
| | G) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| | H) LIST PIPE SIZING TABLES. |
| | |
| | 2) 3.0P & 3.1P: SUBMIT MANUFACTURER?S SPECIFICATIONS |
| | FOR THE NEW COFFEE ROASTER- SECTION 305.1 FBC FG. |
| | PLEASE HIGHLIGHT OR MARKUP THE SPEC TO SHOW THE LISTING |
| | STANDARD, BTU LOAD, AND GAS INPUT PRESSURE. |
| | |
| | 3) 3.0P & 3.1P: PROVIDE COMBUSTION AIR CALCULATIONS FOR |
| | THE COFFEE ROASTER AND INDICATE HOW THE AIR IS BEING |
| | SUPPLIED- SECTION 304.1 FBC FG. |
| | |
| | 4) 3.0P & 3.1P: PROVIDE GAS VENTING PLANS FOR THE |
| | ROASTER- SECTIONS 305.1, 502.1, 502.5, AND 503.1-. THE |
| | DRAWING SPEARS TO INDICATE TWO VENT DUCTS FOR THE |
| | ROASTER THAT ARE PENETRATING THROUGH THE WALL AND |
| | TURNING UPWARD. PLEASE PROVIDE A DIAGRAM AND ELEVATION |
| | VIEW SHOWING THE TYPES AND SIZES OF VENT FLUES OR |
| | DUCTS, HORIZONTAL CONNECTORS, VERTICAL FLUES, AND |
| | TERMINATION CAPS. PLEASE PROVIDE THE VENT TERMINATION |
| | CLEARANCE DISTANCES TO DOOR AND WINDOW OPENINGS INTO |
| | THE BUILDING- SECTIONS 305.1, 403.4, 503.6 & 503.8 FBC |
| | FG. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |