| Plan Review Notes For Permit 21050666 |
| Permit Number |
21050666 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-05-19 08:02:24 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | VIBRO COMPACTION REPORT | | | | | | 1) THE VIBRO COMPACTION REPORT SHOULD NOT BE SUBMITTED | | | WITH THE SHORING/RESHORING DOCUMENTS. IT SHOULD BE A | | | SEPARATE SUBMITTAL WITH IT'S OWN SUBMITTAL NUMBER. THAT | | | WAY IT WILL BE FILED SEPARATELY IN THE RECORDS. FBC | | | AMENDMENTS 107.2.1.3 | | | | | | 2) THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON THE | | | VIBRO COMPACTION REPORT. FS 471 & 61G15 SEE THE | | | SIGNATURE REVIEW. | | | | | | 3) THE VIBRO COMPACTION REPORT IS REQUIRED TO BE | | | REVIEWED BY THE ENGINEER OF RECORD FOR THE PROJECT. THE | | | EOR SHOP REVIEW STAMP IS REQUIRED ON THE VIBRO | | | COMPACTION REPORT. FBC AMENDMENTS 107.3.4 | | | | | | SHORING/RESHORING DOCUMENTS | | | | | | 1) THE SHORING/RESHORING CALCULATIONS AND PLANS ARE | | | REQUIRED TO BE REVIEWED BY THE ENGINEER OF RECORD FOR | | | THE PROJECT. THE EOR SHOP REVIEW STAMP IS REQUIRED ON | | | THE SHORING/RESHORING DOCUMENTS. FBC AMENDMENTS 107.3.4 | | | | | | 2) THE ENGINEER'S DIGITAL SIGNATURE ON THE | | | SHORING/RESHORING CALCULATIONS AND PLANS IS | | | SELF-CERTIFIED. THIRD PARTY CERTIFICATION IS REQUIRED | | | BY THE FLORIDA BOARD OF ENGINEERS. FS 471 & 61G15 SEE | | | THE SIGNATURE REVIEW. | | | | | | |
|