Plan Review Notes
Plan Review Notes For Permit 21050666
Permit Number 21050666
Review Stop B
Sequence Number 1
Notes
Date Text
2021-05-19 08:02:24PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 VIBRO COMPACTION REPORT
  
 1) THE VIBRO COMPACTION REPORT SHOULD NOT BE SUBMITTED
 WITH THE SHORING/RESHORING DOCUMENTS. IT SHOULD BE A
 SEPARATE SUBMITTAL WITH IT'S OWN SUBMITTAL NUMBER. THAT
 WAY IT WILL BE FILED SEPARATELY IN THE RECORDS. FBC
 AMENDMENTS 107.2.1.3
  
 2) THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON THE
 VIBRO COMPACTION REPORT. FS 471 & 61G15 SEE THE
 SIGNATURE REVIEW.
  
 3) THE VIBRO COMPACTION REPORT IS REQUIRED TO BE
 REVIEWED BY THE ENGINEER OF RECORD FOR THE PROJECT. THE
 EOR SHOP REVIEW STAMP IS REQUIRED ON THE VIBRO
 COMPACTION REPORT. FBC AMENDMENTS 107.3.4
  
 SHORING/RESHORING DOCUMENTS
  
 1) THE SHORING/RESHORING CALCULATIONS AND PLANS ARE
 REQUIRED TO BE REVIEWED BY THE ENGINEER OF RECORD FOR
 THE PROJECT. THE EOR SHOP REVIEW STAMP IS REQUIRED ON
 THE SHORING/RESHORING DOCUMENTS. FBC AMENDMENTS 107.3.4
  
 2) THE ENGINEER'S DIGITAL SIGNATURE ON THE
 SHORING/RESHORING CALCULATIONS AND PLANS IS
 SELF-CERTIFIED. THIRD PARTY CERTIFICATION IS REQUIRED
 BY THE FLORIDA BOARD OF ENGINEERS. FS 471 & 61G15 SEE
 THE SIGNATURE REVIEW.
  
  